Error IDs 16#8050 - 16#805F

Manual Collection S7-1500/ET 200MP

ft:publication_title
Manual Collection S7-1500/ET 200MP
Product
ET 200MP
S7-1500
Version
V21
Publication date
03/2026
Language
en-US
Version
21

ErrorID

Validity

Description

Remedy

TO1)

Kin2)

16#8050

✓

-

Illegal encoder number

Technology version < V7.0:

MC_SetSensor: At the "Sensor" parameter, enter a permissible number for the encoder.

Technology version ≥ V7.0:

MC_SetSensor: At the "Sensor" parameter, enter a permissible number (1, 2, 3, 4) for the encoder.

MC_Home: At the "Sensor" parameter, enter a permissible number (0, 1, 2, 3, 4) used for an encoder.

16#8051

✓

-

Illegal number of the reference encoder

Specify a permissible number of the reference encoder for parameter "MC_SetSensor.ReferenceSensor".

If you call the instruction "MC_SetSensor" with parameter "Mode" = 0, enter a different number for the parameter "ReferenceSensor" than for the parameter "Sensor".

16#8055

✓

-

Bit masking not permitted at "MC_SetAxisSTW"

Non-controllable bits are selected in the "STW1 BitMask" and "STW2 BitMask" bit masks.

Only control permissible bits.

16#805A

✓

-

Illegal value of the parameter to be changed

At parameter "ParameterNumber", enter a permissible value for the index of the parameter to be changed.

16#805B

✓

-

Error in the configuration of the hardware limit switch.

Specify a valid tag at the input of the positive/negative HW limit switch.

16#805C

✓

-

Illegal data type of the value to be written.

Specify a valid data type at the parameter "Value".

16#805D

✓

-

  • Direct PROFIdrive data connection from axis or external encoder.

  • Axis is in simulation.

  • Axis is configured as virtual axis.

Configure the Ti, To, TDC communication times only if the PROFIdrive data connection via data block is configured.

16#805E

✓

-

Invalid value for the tag "Actor.RemoveEnableReaction"

Specify a permissible value for the stop mode at the "Remove enable" alarm response.

16#805F

✓

-

Invalid state of the PROFIdrive state machine

Call the "MC_WriteParameter" Motion Control instruction with the parameter in the Profidrive state S1 or S4.