Use the PlcProgram.Read method to read a single variable from a CPU.

To call the PlcProgram.Read method, you need the "read_value" authorization.

Structure of the request

The following table informs you about the properties of the tag to be read.

Table 1. PlcProgram_Read_Request (object)

Name

Required

Data type

Description

var

yes

string

Name of the tag to be read.

mode

no, default is "simple"

string

Enumeration that determines the response format for this method:

  • "simple": Returns tag values according to the "simple" representation (see section Supported data types).

  • "raw": Returns tag values according to the "raw" representation (see section Supported data types).

Examples

In the following example, the user requests a global tag in the "simple" representation.

{

  "var": "\"MotorSpeed\""

}

In the following example, the user requests a data block tag in the "raw" representation.

{

  "var": "\"MyDB\".MyVariable",

  "mode": "raw"

}

Response structure

If the request to the server was successful, the server returns JSON data values.

Examples

The following example shows the result of reading in a tag of type "int" in the "simple" representation.

-42

The following example shows the result of reading in a tag of type "dword" in the "raw" representation.

[ 1, 47, 233, 0 ]

Possible error messages

The following table shows the possible error messages of the PlcProgram.Read method.

Error code

Error message

Meaning

2

Permission denied

The current authentication token is not authorized to call this method.

Log on with a user account that has sufficient privileges to call this method.

4

No resources

The system does not have the necessary resources to read the requested address.

Carry out the request again as soon as sufficient resources are available.

200

Address does not exist

The requested address does not exist or the Web server cannot access it.

201

Invalid address

The name structure of the symbolic address is not correct.

203

Invalid array index

The dimensions and limits of the array indexes do not correspond to the type information of the CPU.

204

Unsupported address

The data type of the address cannot be read.

Note:

Tag access with the methods PlcProgram.Read, PlcProgram.Write, and PlcProgram.Browse

With these methods it is not yet possible to access all tags in firmware version V3.0.

There are selective restrictions when reading tags of technology objects. If access to specific tags is not possible, the API returns the message "unsupported".