General technical specifications

S7-1200 G2 Programmable Logic Controller

ft:publication_title
S7-1200 G2 Programmable Logic Controller
Product
S7-1200
Version
V20
Publication date
12/2024
Language
en-US
Version
20

Standards compliance

The S7-1200 G2 automation system design conforms with the following standards and test specifications. The test criteria for the S7-1200 G2 automation system are based on these standards and test specifications.

Note:

Some S7-1200 G2 devices are not certified to all the following standards, and certification status can change without notice. Most certification approval markings are listed on the device or packaging. You are responsible for determining whether the devices in your system meet the required certifications for your application. For additional information on the certifications of a specific device, consult with a local Siemens representative or visit the Siemens Industry Online Support Web site. Device certificates can be downloaded from the Siemens Industry Online Support Web site.

CE approval

The S7-1200 G2 automation system satisfies requirements and safety related objectives according to the EC directives listed below, and conforms to the harmonized European standards (EN) for the programmable controllers listed in the Official Journals of the European Community.

  • 2014/30/EU "Electromagnetic Compatibility" (EMC Directive)

  • 2014/53/EU "Radio Equipment" (RED Directive)

  • 2014/34/EU "Equipment and protective systems intended for use in potentially explosive atmospheres" (ATEX Directive)

  • 2011/65/EU "Restriction of the use of certain hazardous substances in electrical and electronic equipment" (RoHS Directive)

  • 2006/42/EC "Machinery Directive" for S7-1200 G2 F-CPU, F-SM, and F-SB modules

EU declarations of conformity for the respective authorities are available from:

Siemens AG

Digital Industries

Factory Automation

P.O. Box 1963

D-92209 Amberg

The EU declarations of conformity are also available for download from the Siemens Industry Online Support Web site, under the keyword “Declaration of Conformity”.

Radio Equipment Directive (RED) compliance

The S7-1200 G2 automation system complies with the Radio Equipment Directive (RED) 2014/53/EU. The RED defines NFC tags as radio equipment. The frequency 13.56 MHz is regulated under ETSI EN 300 330 v2.1.1.

UK Conformity Assessed marking

The S7-1200 G2 automation system complies with the designated British standards (BS) for programmable controllers published in the official consolidated list of the British Government. The S7‑1200 G2 automation system meets the requirements and protection targets of the following regulations and related amendments:

  • Electromagnetic Compatibility Regulations 2016 (EMC)

  • Radio Equipment Regulations 2017

  • Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 (ATEX)

  • Regulations on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2012 (RoHS)

  • Supply of Machinery (Safety) Regulations 2008 for S7-1200 G2 F-CPU, F-SM, and F-SB modules

UK Declarations of Conformity for the respective authorities are available from:

Siemens AG

Digital Industries

Factory Automation

P.O. Box 1963

D-92209 Amberg

The UK Declaration of Conformity is also available for download from the Siemens Industry Online Support Web site under the keyword "Declaration of Conformity".

cULus approval

Underwriters Laboratories Inc. complying with:

  • Underwriters Laboratories, Inc.: UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use; Part 1: General Requirements and UL 61010-2-201, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 2-201: Particular Requirements for Control Equipment.

  • Canadian Standards Association: CAN/CSA-C22.2 No. 61010-1-12, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements and CSA C22.2 No. 61010-2-201, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 2-201: Particular Requirements for Control Equipment.

Note:

The SIMATIC S7-1200 G2 series meets the CSA standard.

The cULus logo indicates that the S7-1200 G2 has been examined and certified by Underwriters Laboratories (UL) to the standards referenced above.

cULus HAZ. LOC. approval

Underwriters Laboratories Inc. in accordance with:

  • ANSI/ISA 12.12.01

  • CAN/CSA C22.2 No. 213 (Hazardous Location) APPROVED for use in Class I, Division 2, Group A, B, C, D T4C; Class I, Zone 2, Group IIC T4 Installation Instructions for cULus haz.loc.

  • WARNING – Explosion Hazard – Do not disconnect while circuit is live unless area is known to be non-hazardous.

  • WARNING – Explosion Hazard – Substitution of components can impair suitability for Class I, Division 2 or Zone 2.

  • This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I, Zone 2, Group IIC; or non-hazardous locations.

IMPORTANT EXCEPTION: Some models are de-rated for Ta = 60 °C. See the Technical Specifications of each device for derating information.

ATEX approval

According to EN 60079-7 (Electrical apparatus for potentially explosive atmospheres – Part 7: Increased safety “e”), EN IEC 60079-0 (Electrical apparatus for potentially explosive gas atmospheres – Part 0: General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").

II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)

UL 24 ATEX 3237X

Special conditions of use:

  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.

  • The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN 60079-7.

  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.

IECEx approval

According to IEC 60079-7 (Explosive atmospheres – Part 7: Equipment protection by increased safety “e”), IEC 60079-0 (Explosive atmospheres – Part 0: Equipment – General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").

II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)

IECEx UL 24.0044X

Specific conditions of use:

  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1.

  • The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN IEC 60079-0.

  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.

UKEX approval

According to EN 60079-7 (Explosive atmospheres – Part 7: Equipment protection by increased safety “e”), EN IEC 60079-0 (Explosive atmospheres – Part 0: Equipment – General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").

II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)

UL 24UKEX2991X

Specific conditions of use:

  • The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.

  • The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN 60079-7.

  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.

CCCEx approval

According to GB/T 3836.1 (Explosive atmospheres – Part 1: Equipment – General requirements),GB/T 3836.3 (Explosive atmospheres – Part 3: Equipment protection by increased safety “e”), and GB/T 3836.8 (Explosive atmospheres – Part 8: Equipment protection by type of protection "n" see product marking)

Specific conditions of safety use:

  • The equipment shall only be used in an area of at least pollution degree 2, as defined in GB/T 16935.1.

  • The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with GB/T 3836.3.

  • Transient protection shall be provided that is set at a level not exceeding 140% of the peak value at the supply terminals to the equipment.

Australia and New Zealand - RCM Mark (Regulatory Compliance Mark)

The S7-1200 G2 automation system satisfies the requirements of AS/NZS 2064 standards (Class A).

Eurasian Customs Union approval

EAC (Eurasian Conformity): Declaration of Conformity according to Technical Regulation of Customs Union (TR CU)

Industrial environments

The S7-1200 G2 automation system is designed for use in industrial environments.

Table 1. Industrial environments

Application field

Emission requirements

Immunity requirements

Industrial

EN 61000-6-4

EN 61000-6-2

Environmental conditions

The S7-1200 G2 automation system is suitable for use in weather-proof, fixed locations. The operating conditions are based on requirements of IEC 61131-2:2017.

Table 2. Shipping and storage

Environmental conditions – Shipping and storage conditions (TTH4 and STH4)

EN 60068-2-1, Test Ab, Cold

EN 60068-2-2, Test Dc, Dry heat

-40 °C to 70 °C

EN 60068-2-30, Test Db, Damp heat

25 °C to 55 °C, 95% RH

EN 60068-2-14, Test Na, Temperature shock

-40 °C to 70 °C, dwell time 3 hours, 2 cycles

EN 60068-2-31, Free fall

0.3 m, 5 times, product packaging

Atmospheric pressure

1140 to 540 hPa (corresponding to an altitude of -1000 to

5000 m)

Table 3. Climatic ambient conditions

Environmental conditions – Climatic ambient operating conditions (OTH4)

Ambient temperature

(Inlet Air 25 mm below unit)

‑20 °C to 40 °C       Max. specifications

‑20 °C to 60 °C       With derating

For vertical mounting see individual device specifications.

Minimum temperature for Fail-safe SMs/SBs is 0 °C.

95% non-condensing humidity

Atmospheric pressure

1140 to 540 hPa

(corresponding to an altitude from -1000 to 5000 m)

For altitudes above 2000 m, the maximum permissible ambient temperature must be derated: >2000 m 0.9 factor, >3000 m 0.8 factor, >4000 m 0.7 factor. 5000 m is max allowed altitude.

Effects on the availability of modules at altitude

The higher cosmic radiation present during operation at altitudes above 2000 m affect the failure rate of electronic components. This is what is called a soft-error rate. In rare cases, this can result in a transition of modules to the safe state, especially for fail-safe modules. However, the functional safety of the modules is fully retained.

Concentration of contaminants

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% non-condensing

EN 60068-2-14, Test Nb

(Temperature change)

-20 °C to 60 °C, dwell time 3 hours, 5 cycles

EN 60068-2-78, Test Cab

(Damp heat)

30 °C, 95% RH, 16 hours

EN 60068-2-27

(Shock)

15 g, 11 ms pulse, 6 shocks in each of 3 axes

(when panel mounted)

EN 60068-2-6

(Sinusoidal vibration)

3.5 mm from 5 to 8.4 Hz, 1g from 8.4 to 150 Hz

10 sweeps each axis, 1 octave per minute

(when panel or DIN rail mounted)

Note: In high vibration applications, Siemens recommends panel mounting or the use of a Siemens DIN Rail with DIN Rail End Retainers to secure devices.

Electromagnetic compatibility

Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as intended in an electromagnetic environment and to operate without emitting levels of electromagnetic interference (EMI) that can disturb other electrical devices in the vicinity.

Table 4. Immunity

Electromagnetic compatibility - Immunity per EN 61000-6-2

EN 61000-4-2

Electrostatic discharge

8 kV air discharge to all surfaces

6 kV contact discharge to exposed conductive surfaces

EN 61000-4-3

Radiated, radio-frequency, electromagnetic field immunity test

80 MHz to 1000 MHz, 10 V/m, 80% AM (1 kHz)

1.4 GHz to 6 GHz, 3 V/m, 80% AM (1 kHz)

EN 61000-4-4

Fast transient bursts

2 kV, 5 kHz with coupling network to AC and DC system power

2 kV, 5 kHz with coupling clamp to I/O

EN 61000-4-5

Surge immunity

AC systems - 2 kV common mode, 1 kV differential mode

DC systems - 1 kV common mode, 0.5 kV differential mode

EN 61000-4-6

Conducted disturbances

150 kHz to 80 MHz, 10 V RMS, 80% AM at 1 kHz

EN 61000-4-11

Voltage dips

AC systems

0% for 1 cycle, 40% for 12 cycles, and 70% for 30 cycles at 60 Hz

Table 5. Emissions

Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4

Conducted emissions

AC power ports

0.15 MHz to 0.5 MHz

< 79 dBµV quasi-peak, < 66 dBµV average

0.5 MHz to 30 MHz

< 73 dBµV quasi-peak, < 60 dBµV average

Conducted emissions

DC power ports

0.15 MHz to 0.5 MHz

< 89 dBµV quasi-peak, < 76 dBµV average

0.5 MHz to 30 MHz

< 83 dBµV quasi-peak, < 70 dBµV average

Radiated emissions

30 MHz to 230 MHz

< 40 dBµV/m quasi-peak at 10 m

230 MHz to 1000 MHz

< 47 dBµV/m quasi-peak at 10 m

1000 MHz to 3000 MHz

< 76 dBµV/m peak, < 56 dBµV/m average at 3 m

3000 MHz to 6000 MHz

< 80 dBµV/m peak, < 60 dBµV/m average at 3 m

Insulation

The insulation is designed in accordance with the requirements of IEC 61010-2-201.

Note:

For modules having 24 V DC (SELV / PELV) supply voltage, galvanic isolations are tested with 707 V DC (type test)

Pollution degree / overvoltage category in accordance with IEC 61131-2 and IEC 61000-2-201

  • Pollution degree 2

  • Overvoltage category II

Protection class according to IEC 61131-2 and IEC 61010-2-201

  • Protection class II

Degree of protection

  • IP20 Mechanical Protection, EN 60529

  • Protects against finger contact with high voltage as tested by standard probe. External protection required for dust, dirt, water and foreign objects of < 12.5 mm in diameter.

Rated voltages

The rated voltages are:

  • 24 V DC

  • 120/240 V AC

Warning:

Risks when turning on output power

When a mechanical contact turns on output power to the S7-1200 G2 CPU, or any digital expansion module, it sends a “1” signal to the digital outputs for approximately 50 microseconds.

This could cause unexpected machine or process operation, which could result in death or serious injury to personnel and/or damage to equipment.

You must plan for the "1" signal to the digital outputs.

Reverse voltage protection

Reverse voltage protection circuitry is provided on each terminal pair of +24  V DC power or user input power for CPUs, signal modules (SMs), and signal boards (SBs). It is still possible to damage the system by wiring different terminal pairs in opposite polarities.

Some of the 24 V DC power input ports in the S7-1200 G2 system are interconnected, with a common logic circuit connecting multiple M terminals. For example, the following circuits are interconnected when designated as “not isolated”: the 24 V DC power supply of the CPU, the sensor power of the CPU, the power input for the relay coil of an SM, and the power supply for a non-isolated analog input. All non-isolated M terminals must connect to the same external reference potential.

Warning:

Risks when connecting non-isolated M terminals to different reference potentials.

Connecting non-isolated M terminals to different reference potentials causes unintended current flows that can cause damage or unpredictable operation in the PLC and any connected equipment.

Always ensure that all non-isolated M terminals in an S7-1200 G2 system are connected to the same reference potential.

Failure to comply with these guidelines could cause damage or unpredictable operation, which can result in death or severe personal injury and/or property damage.

DC Outputs

Short-circuit protection circuitry is not provided for DC outputs on CPUs, signal modules (SMs), and signal boards (SBs).

Relay electrical service life

The typical performance data estimated from sample tests is shown below. Actual performance can vary depending upon your specific application. An external protection circuit that is adapted to the load enhances the service life of the contacts. Normally closed contacts have a typical service life of about one-third that of normally open contacts under inductive and lamp load conditions.

Table 6. Typical performance data

Data for selecting an actuator

Continuous thermal current

2 A max.

Switching capacity and life of the contacts

For ohmic load

Voltage

Current

Number of operating cycles (typical)

24 V DC

2.0 A

0.1 million

24 V DC

1.0 A

0.2 million

24 V DC

0.5 A

1.0  million

48 V AC

1.5 A

1.5 million

60 V AC

1.5 A

1.5 million

120 V AC

2.0 A

1.0 million

120 V AC

1.0 A

1.5 million

120 V AC

0.5 A

2.0 million

230 V AC

2.0 A

1.0 million

230 V AC

1.0 A

1.5 million

230 V AC

0.5 A

2.0 million

For inductive load (according to

IEC 947-5-1 DC13/AC15)

Voltage

Current

Number of operating cycles (typical)

24 V DC

2.0 A

0.05 million

24 V DC

1.0 A

0.1 million

24 V DC

0.5 A

0.5 million

24 V AC

1.5 A

1.0 million

48 V AC

1.5 A

1.0 million

60 V AC

1.5 A

1.0 million

120 V AC

2.0 A

0.7 million

120 V AC

1.0 A

1.0 million

120 V AC

0.5 A

1.5 million

230 V AC

2.0 A

0.7 million

230 V AC

1.0 A

1.0 million

230 V AC

0.5 A

1.5 million

Activating a digital input

Possible

Switching frequency

Mechanical

Max. 10 Hz

At ohmic load

Max. 1 Hz

At inductive load (according to IEC 947-5-1 DC13/AC15)

Max. 0.5 Hz

At lamp load

Max. 1Hz

Internal CPU memory retention

The CPU performs operations to extend the life of the internal memory devices that contain the application data. Below is the life expectancy of the internal memory.

  • Lifetime of retentive data and data log data: 10 years

  • Power down retentive data, write cycle endurance: 2 million cycles

  • Data log data, write cycle endurance: 500 million data log entries

Note:

Effect of data logs on internal CPU memory

Each data log write consumes at a minimum 2 KB of memory. If your program writes small amounts of data frequently, it is consuming at least 2 KB of memory on each write. A better implementation would be to accumulate the small data items in a data block (DB), and to write the data block to the data log at less frequent intervals.

If your program writes many data log entries at a high frequency, consider using a replaceable SD memory card.

Use of cellular phones

You can read information from the CPU and write operations to the CPU from the Near Field Communication (NFC) tag by placing your iPhone near the NFC symbol on the S7-1200 G2 CPU.

All S7-1200 G2 CPUs and modules have a scannable QR code lasered on the housing. Use your smartphone's camera to read the QR code. The QR code provides a direct link to the Siemens Industrial Online Support information for your device.

Warning:

Risks when using a cellular phone in close proximity to the S7-1200 G2 CPU

Using a cellular phone in close proximity to an S7-1200 G2 system with cellular and Wi-Fi communications active can cause unpredictable behavior.

To reduce any influence of a cellular phone on the S7-1200 G2 system, and to ensure proper operation of your CPU, place the phone in “Airplane mode” to disable cellular and Wi-Fi before bringing the phone into proximity (<10 cm) of the CPU.

Failure to comply with these guidelines can cause damage or unpredictable operation which could result in severe personal injury, property damage, and/or death.

Warning:

Risks when operating a cellular phone in a hazardous or explosive environment

Do not use a cellular phone in a hazardous or explosive environment unless the phone has been approved for use in such environments.

Failure to comply with these guidelines can cause damage or unpredictable operation which could result in severe personal injury, property damage, and/or death.