Standards compliance
The S7-1200 G2 automation system design conforms with the following standards and test specifications. The test criteria for the S7-1200 G2 automation system are based on these standards and test specifications.
Some S7-1200 G2 devices are not certified to all the following standards, and certification status can change without notice. Most certification approval markings are listed on the device or packaging. You are responsible for determining whether the devices in your system meet the required certifications for your application. For additional information on the certifications of a specific device, consult with a local Siemens representative or visit the Siemens Industry Online Support Web site. Device certificates can be downloaded from the Siemens Industry Online Support Web site.
CE approval
The S7-1200 G2 automation system satisfies requirements and safety related objectives according to the EC directives listed below, and conforms to the harmonized European standards (EN) for the programmable controllers listed in the Official Journals of the European Community.
2014/30/EU "Electromagnetic Compatibility" (EMC Directive)
2014/53/EU "Radio Equipment" (RED Directive)
2014/34/EU "Equipment and protective systems intended for use in potentially explosive atmospheres" (ATEX Directive)
2011/65/EU "Restriction of the use of certain hazardous substances in electrical and electronic equipment" (RoHS Directive)
2006/42/EC "Machinery Directive" for S7-1200 G2 F-CPU, F-SM, and F-SB modules
EU declarations of conformity for the respective authorities are available from:
Siemens AG
Digital Industries
Factory Automation
P.O. Box 1963
D-92209 Amberg
The EU declarations of conformity are also available for download from the Siemens Industry Online Support Web site, under the keyword “Declaration of Conformity”.
Radio Equipment Directive (RED) compliance
The S7-1200 G2 automation system complies with the Radio Equipment Directive (RED) 2014/53/EU. The RED defines NFC tags as radio equipment. The frequency 13.56 MHz is regulated under ETSI EN 300 330 v2.1.1.
UK Conformity Assessed marking
The S7-1200 G2 automation system complies with the designated British standards (BS) for programmable controllers published in the official consolidated list of the British Government. The S7‑1200 G2 automation system meets the requirements and protection targets of the following regulations and related amendments:
Electromagnetic Compatibility Regulations 2016 (EMC)
Radio Equipment Regulations 2017
Equipment and Protective Systems Intended for use in Potentially Explosive Atmospheres Regulations 2016 (ATEX)
Regulations on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2012 (RoHS)
Supply of Machinery (Safety) Regulations 2008 for S7-1200 G2 F-CPU, F-SM, and F-SB modules
UK Declarations of Conformity for the respective authorities are available from:
Siemens AG
Digital Industries
Factory Automation
P.O. Box 1963
D-92209 Amberg
The UK Declaration of Conformity is also available for download from the Siemens Industry Online Support Web site under the keyword "Declaration of Conformity".
cULus approval
Underwriters Laboratories Inc. complying with:
Underwriters Laboratories, Inc.: UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use; Part 1: General Requirements and UL 61010-2-201, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 2-201: Particular Requirements for Control Equipment.
Canadian Standards Association: CAN/CSA-C22.2 No. 61010-1-12, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements and CSA C22.2 No. 61010-2-201, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 2-201: Particular Requirements for Control Equipment.
The SIMATIC S7-1200 G2 series meets the CSA standard.
The cULus logo indicates that the S7-1200 G2 has been examined and certified by Underwriters Laboratories (UL) to the standards referenced above.
cULus HAZ. LOC. approval
Underwriters Laboratories Inc. in accordance with:
ANSI/ISA 12.12.01
CAN/CSA C22.2 No. 213 (Hazardous Location) APPROVED for use in Class I, Division 2, Group A, B, C, D T4C; Class I, Zone 2, Group IIC T4 Installation Instructions for cULus haz.loc.
WARNING – Explosion Hazard – Do not disconnect while circuit is live unless area is known to be non-hazardous.
WARNING – Explosion Hazard – Substitution of components can impair suitability for Class I, Division 2 or Zone 2.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D; Class I, Zone 2, Group IIC; or non-hazardous locations.
IMPORTANT EXCEPTION: Some models are de-rated for Ta = 60 °C. See the Technical Specifications of each device for derating information.
ATEX approval
According to EN 60079-7 (Electrical apparatus for potentially explosive atmospheres – Part 7: Increased safety “e”), EN IEC 60079-0 (Electrical apparatus for potentially explosive gas atmospheres – Part 0: General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").
II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)
UL 24 ATEX 3237X
Special conditions of use:
The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN 60079-7.
Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.
IECEx approval
According to IEC 60079-7 (Explosive atmospheres – Part 7: Equipment protection by increased safety “e”), IEC 60079-0 (Explosive atmospheres – Part 0: Equipment – General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").
II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)
IECEx UL 24.0044X
Specific conditions of use:
The equipment shall only be used in an area of not more than pollution degree 2, as defined in IEC 60664-1.
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN IEC 60079-0.
Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.
UKEX approval
According to EN 60079-7 (Explosive atmospheres – Part 7: Equipment protection by increased safety “e”), EN IEC 60079-0 (Explosive atmospheres – Part 0: Equipment – General requirements), and IEC 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part 15: Equipment protection by type of protection "n").
II 3 G Ex ec IIC T4 Gc (some models are II 3 G Ex ec nC IIC T4 Gc, see product marking)
UL 24UKEX2991X
Specific conditions of use:
The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with EN 60079-7.
Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage value at the supply terminals to the equipment.
CCCEx approval
According to GB/T 3836.1 (Explosive atmospheres – Part 1: Equipment – General requirements),GB/T 3836.3 (Explosive atmospheres – Part 3: Equipment protection by increased safety “e”), and GB/T 3836.8 (Explosive atmospheres – Part 8: Equipment protection by type of protection "n" see product marking)
Specific conditions of safety use:
The equipment shall only be used in an area of at least pollution degree 2, as defined in GB/T 16935.1.
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with GB/T 3836.3.
Transient protection shall be provided that is set at a level not exceeding 140% of the peak value at the supply terminals to the equipment.
Australia and New Zealand - RCM Mark (Regulatory Compliance Mark)
The S7-1200 G2 automation system satisfies the requirements of AS/NZS 2064 standards (Class A).
Eurasian Customs Union approval
EAC (Eurasian Conformity): Declaration of Conformity according to Technical Regulation of Customs Union (TR CU)
Industrial environments
The S7-1200 G2 automation system is designed for use in industrial environments.
Application field |
Emission requirements |
Immunity requirements |
|---|---|---|
Industrial |
EN 61000-6-4 |
EN 61000-6-2 |
Environmental conditions
The S7-1200 G2 automation system is suitable for use in weather-proof, fixed locations. The operating conditions are based on requirements of IEC 61131-2:2017.
Environmental conditions – Shipping and storage conditions (TTH4 and STH4) |
|
|---|---|
EN 60068-2-1, Test Ab, Cold EN 60068-2-2, Test Dc, Dry heat |
-40 °C to 70 °C |
EN 60068-2-30, Test Db, Damp heat |
25 °C to 55 °C, 95% RH |
EN 60068-2-14, Test Na, Temperature shock |
-40 °C to 70 °C, dwell time 3 hours, 2 cycles |
EN 60068-2-31, Free fall |
0.3 m, 5 times, product packaging |
Atmospheric pressure |
1140 to 540 hPa (corresponding to an altitude of -1000 to 5000 m) |
Environmental conditions – Climatic ambient operating conditions (OTH4) |
|
|---|---|
Ambient temperature (Inlet Air 25 mm below unit) |
‑20 °C to 40 °C Max. specifications ‑20 °C to 60 °C With derating For vertical mounting see individual device specifications. Minimum temperature for Fail-safe SMs/SBs is 0 °C. |
95% non-condensing humidity |
|
Atmospheric pressure |
1140 to 540 hPa (corresponding to an altitude from -1000 to 5000 m) For altitudes above 2000 m, the maximum permissible ambient temperature must be derated: >2000 m 0.9 factor, >3000 m 0.8 factor, >4000 m 0.7 factor. 5000 m is max allowed altitude. |
Effects on the availability of modules at altitude |
The higher cosmic radiation present during operation at altitudes above 2000 m affect the failure rate of electronic components. This is what is called a soft-error rate. In rare cases, this can result in a transition of modules to the safe state, especially for fail-safe modules. However, the functional safety of the modules is fully retained. |
Concentration of contaminants |
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% non-condensing |
EN 60068-2-14, Test Nb (Temperature change) |
-20 °C to 60 °C, dwell time 3 hours, 5 cycles |
EN 60068-2-78, Test Cab (Damp heat) |
30 °C, 95% RH, 16 hours |
EN 60068-2-27 (Shock) |
15 g, 11 ms pulse, 6 shocks in each of 3 axes (when panel mounted) |
EN 60068-2-6 (Sinusoidal vibration) |
3.5 mm from 5 to 8.4 Hz, 1g from 8.4 to 150 Hz 10 sweeps each axis, 1 octave per minute (when panel or DIN rail mounted) Note: In high vibration applications, Siemens recommends panel mounting or the use of a Siemens DIN Rail with DIN Rail End Retainers to secure devices. |
Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as intended in an electromagnetic environment and to operate without emitting levels of electromagnetic interference (EMI) that can disturb other electrical devices in the vicinity.
Electromagnetic compatibility - Immunity per EN 61000-6-2 |
|
|---|---|
EN 61000-4-2 Electrostatic discharge |
8 kV air discharge to all surfaces 6 kV contact discharge to exposed conductive surfaces |
EN 61000-4-3 Radiated, radio-frequency, electromagnetic field immunity test |
80 MHz to 1000 MHz, 10 V/m, 80% AM (1 kHz) 1.4 GHz to 6 GHz, 3 V/m, 80% AM (1 kHz) |
EN 61000-4-4 Fast transient bursts |
2 kV, 5 kHz with coupling network to AC and DC system power 2 kV, 5 kHz with coupling clamp to I/O |
EN 61000-4-5 Surge immunity |
AC systems - 2 kV common mode, 1 kV differential mode DC systems - 1 kV common mode, 0.5 kV differential mode |
EN 61000-4-6 Conducted disturbances |
150 kHz to 80 MHz, 10 V RMS, 80% AM at 1 kHz |
EN 61000-4-11 Voltage dips |
AC systems 0% for 1 cycle, 40% for 12 cycles, and 70% for 30 cycles at 60 Hz |
Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4 |
||
|---|---|---|
Conducted emissions AC power ports |
0.15 MHz to 0.5 MHz |
< 79 dBµV quasi-peak, < 66 dBµV average |
0.5 MHz to 30 MHz |
< 73 dBµV quasi-peak, < 60 dBµV average |
|
Conducted emissions DC power ports |
0.15 MHz to 0.5 MHz |
< 89 dBµV quasi-peak, < 76 dBµV average |
0.5 MHz to 30 MHz |
< 83 dBµV quasi-peak, < 70 dBµV average |
|
Radiated emissions |
30 MHz to 230 MHz |
< 40 dBµV/m quasi-peak at 10 m |
230 MHz to 1000 MHz |
< 47 dBµV/m quasi-peak at 10 m |
|
1000 MHz to 3000 MHz |
< 76 dBµV/m peak, < 56 dBµV/m average at 3 m |
|
3000 MHz to 6000 MHz |
< 80 dBµV/m peak, < 60 dBµV/m average at 3 m |
|
Insulation
The insulation is designed in accordance with the requirements of IEC 61010-2-201.
For modules having 24 V DC (SELV / PELV) supply voltage, galvanic isolations are tested with 707 V DC (type test)
Pollution degree / overvoltage category in accordance with IEC 61131-2 and IEC 61000-2-201
Pollution degree 2
Overvoltage category II
Protection class according to IEC 61131-2 and IEC 61010-2-201
Protection class II
Degree of protection
IP20 Mechanical Protection, EN 60529
Protects against finger contact with high voltage as tested by standard probe. External protection required for dust, dirt, water and foreign objects of < 12.5 mm in diameter.
Rated voltages
The rated voltages are:
24 V DC
120/240 V AC
Risks when turning on output power
When a mechanical contact turns on output power to the S7-1200 G2 CPU, or any digital expansion module, it sends a “1” signal to the digital outputs for approximately 50 microseconds.
This could cause unexpected machine or process operation, which could result in death or serious injury to personnel and/or damage to equipment.
You must plan for the "1" signal to the digital outputs.
Reverse voltage protection
Reverse voltage protection circuitry is provided on each terminal pair of +24 V DC power or user input power for CPUs, signal modules (SMs), and signal boards (SBs). It is still possible to damage the system by wiring different terminal pairs in opposite polarities.
Some of the 24 V DC power input ports in the S7-1200 G2 system are interconnected, with a common logic circuit connecting multiple M terminals. For example, the following circuits are interconnected when designated as “not isolated”: the 24 V DC power supply of the CPU, the sensor power of the CPU, the power input for the relay coil of an SM, and the power supply for a non-isolated analog input. All non-isolated M terminals must connect to the same external reference potential.
Risks when connecting non-isolated M terminals to different reference potentials.
Connecting non-isolated M terminals to different reference potentials causes unintended current flows that can cause damage or unpredictable operation in the PLC and any connected equipment.
Always ensure that all non-isolated M terminals in an S7-1200 G2 system are connected to the same reference potential.
Failure to comply with these guidelines could cause damage or unpredictable operation, which can result in death or severe personal injury and/or property damage.
DC Outputs
Short-circuit protection circuitry is not provided for DC outputs on CPUs, signal modules (SMs), and signal boards (SBs).
Relay electrical service life
The typical performance data estimated from sample tests is shown below. Actual performance can vary depending upon your specific application. An external protection circuit that is adapted to the load enhances the service life of the contacts. Normally closed contacts have a typical service life of about one-third that of normally open contacts under inductive and lamp load conditions.
Data for selecting an actuator |
|||
|---|---|---|---|
Continuous thermal current |
2 A max. |
||
Switching capacity and life of the contacts |
|||
For ohmic load |
Voltage |
Current |
Number of operating cycles (typical) |
24 V DC |
2.0 A |
0.1 million |
|
24 V DC |
1.0 A |
0.2 million |
|
24 V DC |
0.5 A |
1.0 million |
|
48 V AC |
1.5 A |
1.5 million |
|
60 V AC |
1.5 A |
1.5 million |
|
120 V AC |
2.0 A |
1.0 million |
|
120 V AC |
1.0 A |
1.5 million |
|
120 V AC |
0.5 A |
2.0 million |
|
230 V AC |
2.0 A |
1.0 million |
|
230 V AC |
1.0 A |
1.5 million |
|
230 V AC |
0.5 A |
2.0 million |
|
For inductive load (according to IEC 947-5-1 DC13/AC15) |
Voltage |
Current |
Number of operating cycles (typical) |
24 V DC |
2.0 A |
0.05 million |
|
24 V DC |
1.0 A |
0.1 million |
|
24 V DC |
0.5 A |
0.5 million |
|
24 V AC |
1.5 A |
1.0 million |
|
48 V AC |
1.5 A |
1.0 million |
|
60 V AC |
1.5 A |
1.0 million |
|
120 V AC |
2.0 A |
0.7 million |
|
120 V AC |
1.0 A |
1.0 million |
|
120 V AC |
0.5 A |
1.5 million |
|
230 V AC |
2.0 A |
0.7 million |
|
230 V AC |
1.0 A |
1.0 million |
|
230 V AC |
0.5 A |
1.5 million |
|
Activating a digital input |
Possible |
||
Switching frequency |
|||
Mechanical |
Max. 10 Hz |
||
At ohmic load |
Max. 1 Hz |
||
At inductive load (according to IEC 947-5-1 DC13/AC15) |
Max. 0.5 Hz |
||
At lamp load |
Max. 1Hz |
||
Internal CPU memory retention
The CPU performs operations to extend the life of the internal memory devices that contain the application data. Below is the life expectancy of the internal memory.
Lifetime of retentive data and data log data: 10 years
Power down retentive data, write cycle endurance: 2 million cycles
Data log data, write cycle endurance: 500 million data log entries
Effect of data logs on internal CPU memory
Each data log write consumes at a minimum 2 KB of memory. If your program writes small amounts of data frequently, it is consuming at least 2 KB of memory on each write. A better implementation would be to accumulate the small data items in a data block (DB), and to write the data block to the data log at less frequent intervals.
If your program writes many data log entries at a high frequency, consider using a replaceable SD memory card.
Use of cellular phones
You can read information from the CPU and write operations to the CPU from the Near Field Communication (NFC) tag by placing your iPhone near the NFC symbol on the S7-1200 G2 CPU.
All S7-1200 G2 CPUs and modules have a scannable QR code lasered on the housing. Use your smartphone's camera to read the QR code. The QR code provides a direct link to the Siemens Industrial Online Support information for your device.
Risks when using a cellular phone in close proximity to the S7-1200 G2 CPU
Using a cellular phone in close proximity to an S7-1200 G2 system with cellular and Wi-Fi communications active can cause unpredictable behavior.
To reduce any influence of a cellular phone on the S7-1200 G2 system, and to ensure proper operation of your CPU, place the phone in “Airplane mode” to disable cellular and Wi-Fi before bringing the phone into proximity (<10 cm) of the CPU.
Failure to comply with these guidelines can cause damage or unpredictable operation which could result in severe personal injury, property damage, and/or death.
Risks when operating a cellular phone in a hazardous or explosive environment
Do not use a cellular phone in a hazardous or explosive environment unless the phone has been approved for use in such environments.
Failure to comply with these guidelines can cause damage or unpredictable operation which could result in severe personal injury, property damage, and/or death.