ET 200SP as an IO device

SIMATIC ET 200SP Manual Collection

ft:publication_title
SIMATIC ET 200SP Manual Collection
Product
ET 200SP
Version
V20
Publication date
07/2024
Language
en-US
Version
20

Configuration example

To use the ET 200SP distributed I/O system as an IO device, you need the IM 155‑6 PNxx interface module.

Figure 1. ET 200SP as an IO device

You can find information on further configuration variants of the ET 200SP distributed I/O system in redundancy mode in section "Configuration variants" of the Redundant System S7-1500R/H System Manual.

Commissioning procedure

For commissioning of the ET 200SP distributed I/O system as an IO device on the PROFINET IO, we recommend the following procedure:

Table 1. Procedure for commissioning the ET 200SP as an IO device for PROFINET IO

Step

Procedure

See ...

1

Installing ET 200SP

Section Installation

2

Connecting ET 200SP

  • Supply voltages

  • PROFINET IO

  • Sensors and actuators

Section Wiring

4

Configuring IO controller

Documentation of the IO controller

5

Checking the protective measures

-

6

Switching on supply voltages for the IO controller

Documentation of the IO controller

7

Switching on supply voltages for IO devices

Interface module Manual

8

Downloading the configuration to the IO controller

STEP 7 online help

9

Switching IO controller to RUN mode

Documentation of the IO controller

10

Checking LEDs

Interface module Manual

11

Testing inputs and outputs

The following functions are helpful: Monitoring and modifying tags, testing with program status, forcing, controlling the outputs. Refer to section Test and service functions