ErrorID |
Validity |
Description |
Remedy |
|
|---|---|---|---|---|
|
TO1) |
Kin2) |
|||
|
16#8040 |
✓ |
- |
Illegal value for start position of output cam |
Specify a permissible value for the start position of the output cam for parameter "OnPosition". |
|
16#8041 |
✓ |
- |
Illegal value for end position of distance output cam |
Specify a permissible value for the end position of the distance output cam for parameter "OffPosition". |
|
16#8042 |
✓ |
- |
Illegal value for switch-on duration of time-based output cam |
Specify a permissible value for the switch-on duration of the time-based output cam for parameter "Duration". |
|
16#8043 |
✓ |
- |
Illegal value for force/torque limiting |
Specify a value within the permissible range at the "Limit" parameter. Permitted integer values: -2147483648 to 2147483648 |
|
16#8044 |
✓ |
- |
The axis is not configured for torque reduction. |
Select drive telegram 102, 103, 105 or 106 |
|
16#8045 |
✓ |
- |
The job cannot be executed because a job for traveling to fixed stop is active. |
Switchover to non-position-controlled mode is not possible during active travel to fixed stop. |
|
16#8046 |
✓ |
- |
The "MC_TorqueLimiting" job cannot be deactivated in the "InClamping" state. |
Retract the axis and deactivate "MC_TorqueLimiting". |
|
16#8047 |
✓ |
- |
The motion results in a fixed stop. |
Only motions away from the fixed stop are permitted. |
|
16#8048 |
✓ |
- |
The job cannot be executed because a "MC_Stop" job is active. |
A "MC_Stop" job is active with "Execute" = TRUE. Reset the job with the parameter "Execute" = FALSE. |
|
16#804A |
✓ |
- |
Illegal value for additive torque setpoint |
Specify a permissible value for the additive torque setpoint at the "Value" parameter. |
|
16#804B |
✓ |
- |
Illegal value for torque high limit |
Specify a permissible value for the high limit of the torque at the "UpperLimit" parameter. |
|
16#804C |
✓ |
- |
Illegal value for torque low limit |
Specify a permissible value for the low limit of the torque at the "LowerLimit" parameter. |
|
16#804D |
✓ |
- |
The value of the high limit of the torque is less than or equal to the value of the low limit of the torque. |
Adapt the values of the "UpperLimit" and "LowerLimit" parameters so that the high limit of the torque is greater than the value of the low limit of the torque. |
|
16#804E |
✓ |
- |
The job cannot be executed because a "MC_TorqueLimiting" job is active. |
Exit the setting of the high and low torque limits. Restart the "MC_TorqueLimiting" job. |
|
The job cannot be executed because a "MC_TorqueRange" job is active. |
Stop the force/torque limit or fixed stop detection. Restart the "MC_TorqueRange" job. |
|||
|
16#804F |
✓ |
- |
The axis is not configured for additional torque values. |
Use supplemental telegram 750. |