List of ErrorIDs and ErrorInfos (technology objects V4...5)

The following table lists all ErrorIDs and ErrorInfos that can be indicated in Motion Control instructions. In addition to the cause of the error, remedies for eliminating the error are also listed.

Depending on the error reaction, the axis is stopped in the case of operating errors with stop of axis. The following error reactions are possible:

  • Remove enable

    The setpoint 0 is output and the enable is removed. The axis is braked depending on the configuration in the drive, and is brought to a standstill.

  • Stop with emergency stop ramp

    Active motion commands are aborted. The axis is braked with the emergency stop deceleration configured under "Technology object > Extended parameters > Dynamics > Emergency stop ramp" without any jerk limit and brought to a standstill.

Operating error with axis stop

ErrorID

ErrorInfo

Description

Remedy

Error reaction

16#8000

Drive error, loss of "Drive ready"

-

16#0001

-

Acknowledge error with instruction "MC_Reset"; provide drive signal; restart command, if necessary

 

16#8001

SW low limit switch has been tripped

-

16#000E

The position of the SW low limit switch was reached with the currently configured deceleration

Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the SW limit switch

16#000F

The position of the SW low limit switch was reached with the emergency stop deceleration

16#0010

The position of the SW low limit switch was exceeded with the emergency stop deceleration

Remove enable

16#8002

SW high limit switch has been tripped

-

16#000E

The position of the SW high limit switch was reached with the currently configured deceleration

Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the SW limit switch

16#000F

The position of the SW high limit switch was reached with the emergency stop deceleration

16#0010

The position of the SW high limit switch was exceeded with the emergency stop deceleration

Remove enable

16#8003

HW low limit switch was reached

For drive connection via PTO (Pulse Train Output):

Stop with emergency stop ramp

For drive connection via PROFIdrive/analog output:

Remove enable

16#000E

The HW low limit switch was reached. The axis was stopped with the emergency stop deceleration.

(The homing switch was not found during an active homing procedure)

Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the HW limit switch.

16#8004

HW high limit switch was reached

For drive connection via PTO (Pulse Train Output):

Stop with emergency stop ramp

For drive connection via PROFIdrive/analog output:

Remove enable

16#000E

The HW high limit switch was reached. The axis was stopped with the emergency stop deceleration.

(The homing switch was not found during an active homing procedure)

Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the HW limit switch.

16#8005

PTO / HSC are already being used by another axis

-

16#0001

-

The axis was configured incorrectly:

Correct the configuration of the PTO (Pulse Train Output) / HSC (High Speed Counter) and download it to the controller

More than one axis is to run with one PTO :

Another axis is using the PTO / HSC. If the current axis is to assume the control, the other axis must be disabled with "MC_Power" Enable = FALSE.
(see also Using multiple axes with the same PTO)

16#8006

A communication error has occurred in the axis control panel

Remove enable

16#0012

A timeout has occurred.

Check the cable connection and press the "Manual control" button again

16#8007

The axis cannot be enabled

-

16#0025

Restarting

Wait until the axis restart is complete.

16#0026

Executing loading process in RUN mode

Wait until the loading process is complete.

16#8008

Invalid direction of motion

-

 

16#002E

The selected motion direction is not allowed.

  • Adjust the motion direction and restart the command.

  • Adjust the allowed direction of rotation in the technology object configuration under "Extended parameters > Mechanics". Restart the command.

16#002F

A reversing motion is not possible with the selected motion direction.

16#8009

Reference switch/encoder zero mark not found

Stop with emergency stop ramp

 

16#0033

Error in the configuration, hardware or installation of the encoder or at the homing switch.

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#800A

Alarm message from encoder

Remove enable

 

16#0001

-

Check the device with regard to function, connections and I/Os.

16#0034

Hardware error at encoder

16#0035

Encoder dirty

16#0036

Error during reading of encoder absolute value

Compare the encoder type in the drive or encoder parameter P979 with the configuration data of the technology object.

16#0037

Zero mark monitoring of the encoder

Encoder reports error in zero mark monitoring (fault code 0x0002 in Gx_XIST2, see PROFIdrive profile).

Check the plant for electromagnetic compatibility (EMC).

16#0038

Encoder is in "Parking" state

  • Search for the cause of the error in the connected drive or encoder.

  • Check whether the error message was possibly triggered by a commissioning action at the drive or encoder.

16#0040

PROFIdrive: Encoder on bus failed (station failure).

Check the device with regard to function, connections and I/Os.

16#800B

Range violation of the position

Remove enable

 

16#0039

Range violation in positive direction

Home the axis to a valid actual value range.

16#003A

Range violation in negative direction

16#003B

The change of the actual position in a position control clock cycle is longer than the length.

Adjust the modulo length of the employed encoder.

16#800C

Alarm message from drive

Remove enable

 

16#0001

-

Check the device with regard to function, connections and I/Os.

In the "Tuning" dialog box, select a smaller gain (Kv).

16#003C

PROFIdrive: Drive signal "Control requested" failed.

16#003D

PROFIdrive/analog drive connection: Drive has shut down.

16#003E

PROFIdrive: Drive on bus failed (station failure)

16#800D

The permitted following error was exceeded

Remove enable

 

16#0001

-

  • Check the configuration of the control loop.

  • Check the direction signal of the encoder.

  • Check the configuration of following error monitoring.

16#800E

Error at the hardware limit switch

Remove enable

 

16#0042

Illegal free travel direction with active hardware limit switch

The programmed direction of movement is disabled due to the active hardware limit switch.

Retract the axis in the opposite direction.

16#0043

Hardware limit switch polarity is reversed, axis cannot be freed

Check the mechanical configuration of the hardware limit switch.

16#0044

Both hardware limit switches are active, axis cannot be freed

16#800F

Error in target range

Remove enable

 

16#0045

Target range not reached

Target range was not reached within the positioning tolerance time.

  • Check the configuration of the position monitoring.

  • Check the configuration of the control loop.

16#0046

Exit target range again

The target range was exited within the minimum dwell time.

  • Check the configuration of the position monitoring.

  • Check the configuration of the control loop.

16#8010

Position of the SW low limit switch is greater than that of the SW high limit switch when the axis is not a modulo axis

Remove enable

 

16#0001

-

Change the position of the software limit switches.

Operating error without axis stop

ErrorID

ErrorInfo

Description

Remedy

16#8200

Axis is not enabled

16#0001

-

Enable the axis; restart the command

16#8201

Axis has already been enabled by another " MC_Power " instance

16#0001

-

Enable the axis with only one "MC_Power" instance

16#8202

The maximum number of simultaneous motion control commands has been exceeded (max. 200 commands for drive connection via PTO (Pulse Train Output) , max. 100 commands for drive connection via PROFIdrive /analog output)

16#0001

-

Reduce the number of simultaneously active commands; restart the command

A command is active if parameter "Busy" = TRUE in the Motion Control instruction.

16#8203

Axis is currently operated in "Manual control" (axis control panel)

16#0001

-

Exit "Manual control"; restart the command

16#8204

Axis is not homed

16#0001

-

Home the axis with instruction "MC_Home"; restart the command

16#8205

The axis is currently controlled by the user program (the error is only displayed in the axis control panel)

16#0013

The axis is enabled in the user program

Disable axis with instruction "MC_Power" and select "Manual control" again in the axis control panel

16#8206

Technology object not activated yet

16#0001

-

Enable the axis with instruction "MC_Power" Enable = TRUE or enable the axis in the axis control panel.

16#8207

Command rejected

16#0016

Active homing is running; another homing method cannot be started.

Wait for active homing to finish or abort the active homing with a motion command, for example, "MC_Halt".

16#0018

The axis cannot be moved with a command table while it is being actively or passively homed.

Wait until direct or passive homing is complete.

16#0019

The axis cannot be actively or passively homed while a command table is being processed.

Wait for command table to finish or abort the command table with a motion command, for example, "MC_Halt".

16#0052

The specified position exceeds the numerical limit.

Enter a valid position value at the Motion Control instruction.

16#0053

The axis is ramping up.

Wait until the axis is ready for operation.

16#0054

Actual value is invalid

To execute a "MC_Home" command, the actual values must be valid.

Check the status of the actual values. The variable of the technology object <Axis name>."StatusSensor.State" must show the value 2 (valid).

16#8208

Difference between maximum and start/stop velocity is invalid

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000A

Value is less than or equal to 0.

16#8209

Invalid acceleration for technology object "Axis"

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000A

Value is less than or equal to 0.

16#820A

It is not possible to restart the axis

16#0013

The axis is enabled in the user program

Disable the axis with the "MC_Power" instruction; restart again

16#0027

The axis is currently being operated in "Manual control" (axis control panel)

Exit "Manual control"; restart again

16#002C

The axis is not disabled.

Disable the axis; restart the command

16#0047

The technology object is not ready for restart.

Download the project again.

16#0048

Condition for restart of the technology object is not satisfied.

Disable the technology object.

16#820B

It is not possible to execute the command table

16#0026

Executing loading process in RUN mode

Wait until the loading process is complete.

16#820C

No configuration available

 

16#0001

-

Internal error

Contact the hotline.

Block parameter error

ErrorID

ErrorInfo

Description

Remedy

16#8400

Invalid value at parameter " Position " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#8401

Invalid value at parameter " Distance " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#8402

Invalid value at parameter " Velocity " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#0008

Value is greater than the configured maximum velocity

16#0009

Value is less than the configured start/stop velocity

16#0024

Value is less than 0

16#8403

Invalid value at parameter " Direction " of the Motion Control instruction

 

16#0011

The selection value is invalid

Correct the selection value; restart the command

16#8404

Invalid value at parameter " Mode " of the Motion Control instruction

 

16#0011

The selection value is invalid

Correct the selection value; restart the command

16#0015

Active/passive homing is not configured

Correct the configuration and download it to the controller; enable the axis and restart the command

16#0017

The direction reversal is activated at the hardware limit switch, despite the fact that the hardware limit switches are disabled

  • Activate the HW limit switch using the variable <Axis name>.PositionLimitsHW.Active = TRUE, restart the command

  • Correct the configuration and download it to the controller; enable the axis and restart the command

16#0055

Invalid mode at incremental encoder

Start a homing process for an incremental encoder using parameter "Mode" = 0, 1, 2, 3.

16#0056

Invalid mode at absolute encoder

Passive and active homing ("Mode" = 2, 3) are not possible for an absolute value encoder.

Start a homing process for an absolute encoder using parameter "Mode" = 0, 1.

16#8405

Invalid value at parameter " StopMode " of the Motion Control instruction

 

16#0011

The selection value is invalid

Correct the selection value; enable the axis again

16#8406

Simultaneous forward and backward jogging is not allowed

 

16#0001

-

Take steps to ensure that parameters "JogForward" and "JogBackward" do not have signal status TRUE simultaneously; restart the command.

16#8407

Switching to another axis with instruction " MC_Power " is only permitted after disabling the active axis.

 

16#0001

-

Disable the active axis; it is then possible to switch to the other axis and enable it.

16#8408

Invalid value at parameter " Axis " of the Motion Control instruction

 

16#001A

The specified value does not match the required technology object version

Correct the value; restart the command

16#001B

The specified value does not match the required technology object type

16#001C

The specified value is not a Motion Control technology data block

16#8409

Invalid value at parameter " CommandTable " of the Motion Control instruction

 

16#001A

The specified value does not match the required technology object version

Correct the value; restart the command

16#001B

The specified value does not match the required technology object type

16#001C

The specified value is not a Motion Control technology data block

16#840A

Invalid value at parameter " StartStep " of the Motion Control instruction

 

16#000A

Value is less than or equal to 0.

Correct the value; restart the command

16#001D

The start step is greater than the end step

16#001E

Value is greater than 32

16#840B

Invalid value at parameter " EndStep " of the Motion Control instruction

 

16#000A

Value is less than or equal to 0.

Correct the value; restart the command

16#001E

Value is greater than 32

16#840C

Invalid value at parameter " RampUpTime " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#0005

Value is outside the number range (greater than 1.0E12)

16#000A

Value is less than or equal to 0.

16#840D

Invalid value at parameter " RampDownTime " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000A

Value is less than or equal to 0.

16#840E

Invalid value at parameter " EmergencyRampTime " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000A

Value is less than or equal to 0.

16#840F

Invalid value at parameter " JerkTime " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000A

Value is less than or equal to 0.

16#8410

Invalid value at parameter " Parameter " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

16#000B

Address is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0028

Data type of VARIANT pointer "Parameter" and "Value" do not match.

Use a suitable data type; restart command

16#0029

VARIANT pointer "Parameter" does not point to a data block of the technology object.

Correct the VARIANT pointer; restart the command

16#002A

The value at the VARIANT pointer "Parameter" cannot be read.

Correct the VARIANT pointer; restart the command

16#002B

The value at the VARIANT pointer "Parameter" cannot be written.

Correct the VARIANT pointer or value; restart the command

16#002C

The axis is not disabled.

Disable the axis; restart the command

16#8411

Invalid value at parameter " Value " of the Motion Control instruction

 

16#0002

The value has an invalid number format

Correct the value; restart the command

Configuration error of the axis

ErrorID

ErrorInfo

Description

Remedy

16#8600

Parameter assignment of pulse generator ( PTO is invalid

 

16#000B

The address is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0014

The selected hardware is used by another application

16#8601

Parameter assignment of the high-speed counter ( HSC ) is invalid

 

16#000B

The address is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0014

The selected hardware is used by another application

16#8602

Invalid parameter assignment of "Enable output"

 

16#000B

The address is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8603

Invalid parameter assignment of "Ready input"

 

16#000B

The address is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8604

Invalid "Pulses per motor revolution" value

 

16#000A

Value is less than or equal to 0

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8605

Invalid "Distance per revolution" value

 

16#0002

The value has an invalid number format

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0005

Value is outside the number range (greater than 1E+12)

16#000A

Value is less than or equal to 0

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8606

Invalid "Start/stop velocity" value

 

16#0002

The value has an invalid number format

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0003

Value is higher than the hardware high limit

16#0004

Value is lower than the hardware low limit

16#0007

The start/stop velocity is greater than the maximum velocity

16#8607

Invalid "maximum velocity" value

 

16#0002

The value has an invalid number format

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#0003

Value is higher than the hardware high limit

16#0004

Value is lower than the hardware low limit

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8608

Invalid "Acceleration" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0003

Value is higher than the hardware high limit

16#0004

Value is lower than the hardware low limit

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8609

Invalid "Deceleration" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0003

Value is higher than the hardware high limit

16#0004

Value is lower than the hardware low limit

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#860A

Invalid "Emergency stop deceleration" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0003

Value is higher than the hardware high limit

16#0004

Value is lower than the hardware low limit

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#860B

Value for position of the SW low limit switch is invalid

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#0030

The position value of the software low limit switch is greater than that of the software high limit switch

16#860C

Value for position of the SW high limit switch is invalid

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#860D

Invalid address of the HW low limit switch

 

16#000B

Invalid address

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#000C

The address of the falling edge is invalid

16#000D

The address of the rising edge is invalid

16#860E

Invalid address of the HW high limit switch

 

16#000B

Invalid address

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#000C

The address of the falling edge is invalid

16#000D

The address of the rising edge is invalid

16#860F

Invalid "home position offset" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8610

Invalid "approach velocity" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0008

The velocity is greater than the maximum velocity

16#0009

The velocity is less than the start/stop velocity

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8611

Invalid "Homing velocity" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0008

The velocity is greater than the maximum velocity

16#0009

The velocity is less than the start/stop velocity

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8612

Invalid address of the homing switch

 

16#000B

Invalid address

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#000C

The address of the falling edge is invalid

16#000D

The address of the rising edge is invalid

16#8613

During active homing, direction reversal at the hardware limit switch is activated although the hardware limit switches are not configured

 

16#0001

-

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8614

Invalid "Jerk" value

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#001F

Value is greater than the maximum jerk

16#0020

Value is less than the minimum jerk

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8615

Value for "Unit of measurement" is invalid

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8616

Address of homing switch is invalid (passive homing as of V4)

 

16#0011

The selection value is invalid

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8617

Value of tag <Axis name>. Sensor.Sensor[1].ActiveHoming.Mode is invalid

 

16#0011

The selection value is invalid

(Valid value: 2 = Homing via digital input)

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8618

Value of tag <Axis name>. Sensor.Sensor[1].PassiveHoming.Mode is invalid

 

16#0011

The selection value is invalid

(Valid value: 2 = Homing via digital input)

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8619

Value of tag <Axis name>. Actor.Type is invalid

 

16#0011

The selection value is invalid

(Valid value: 2 = Connection via pulse interface)

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#861A

Value for "Permitted direction of rotation" is invalid

 

16#0011

The selection value is invalid

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#002D

"Both directions" not permitted with direction output switched off

16#861B

Faulty load gear factors

 

16#0031

Valid is invalid.

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#861C

Illegal combination of data for homing with incremental encoder

 

16#0031

Valid is invalid.

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#861D

The set encoder mounting type is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].MountingMode

 

16#0011

The selection value is invalid

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#861E

The configuration of the measuring wheel circumference of the encoder is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.DistancePerRevolution

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#861F

The configuration for the resolution of the linear encoder is faulty. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.Resolution

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8620

The configured fine resolution for Gx_XIST1 is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist1

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8621

The set fine resolution for Gx_XIST1 in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist1 is not consistent with the setting in PROFIdrive parameter P979

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8622

Invalid value for the configuration date <Axis name>. Actor.Interface.AddressIn or <Axis name>. Actor.Interface.AddressOut

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8623

The value set in the tag <axis name>. Sensor.Sensor[1].Type is invalid.

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8624

The set encoder system is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].System

 

16#0011

The selection value is invalid

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8625

Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.MinDwellTime

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8626

Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.Window

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8627

The configuration of the PROFIdrive interface of the actual value is faulty. Invalid value in <Axis name>. Sensor.Sensor[1].Interface.AddressIn or <Axis name>. Sensor.Sensor[1].Interface.AddressOut

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8628

Faulty controller factors

 

16#0030

Value has an incorrect number format or is outside the valid number range

The value for the gain or the precontrol of the control loop is faulty.

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with the "MC_Reset" instruction and restart the command, if necessary>.PositionControl.Kv, <axis name>.PositionControl.Kpc)

16#8629

Limit for standstill signal is faulty. Invalid value in <Axis name>. StandStillSignal.VelocityThreshold

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#862A

Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.ToleranceTime

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#862B

Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP cycle

 

16#0030

Value has an incorrect number format or is outside the valid number range

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#862C

Parameter of standstill monitoring is faulty. Invalid value in <Axis name>. StandStillSignal.MinDwellTime

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#862D

Parameter of following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MinValue

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#862E

Invalid value for the configuration date <Axis name>. Modulo.Length

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#862F

Invalid value for the configuration date <Axis name>. Modulo.StartValue

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8630

Invalid value for the configuration date <Axis name>. Actor.DriveParameter.ReferenceSpeed

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8631

The set fine resolution for Gx_XIST2 is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist2

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8632

The number of determinable encoder revolutions is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.DeterminableRevolutions

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8633

The specified approach direction of the homing switch for passive homing is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].PassiveHoming.Direction

   

 

16#8634

Parameter of the following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MaxValue

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8635

Parameter of the following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MinVelocity

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8636

Controller factor is incorrect. Invalid value of the precontrol factor <Axis name>. PositionControl.Kpc

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#8637

Invalid value for the configuration date <Axis name>. Sensor.Sensor[1].Interface.Type

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8638

Invalid value for the configuration date <Axis name>. Sensor.Sensor[1].Interface.HSC

 

16#0011

The selection value is invalid

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#8639

Error at the drive

 

16#0049

Configuration error at device

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#004A

The technology needs a smaller servo clock.

Internal system error.

Check the project for consistency and reload it into the controller.

16#004B

Device driver not initialized during ramp-up.

To enable a technology object, the actuator driver must be initialized.

Execute the command again later.

16#863A

Communication to the drive is faulty

 

16#004C

Configuration error at device

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#004D

The device driver needs a smaller servo clock.

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#004E

Error in internal communication with the device

Check the project for consistency and reload it into the controller.

16#863B

Error at encoder

 

16#0049

Configuration error at device

Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

16#004A

The technology needs a smaller servo clock.

Internal system error.

Check the project for consistency and reload it into the controller.

16#004B

Device driver not initialized during ramp-up.

To enable a technology object, the actuator driver must be initialized.

Execute the command again later.

16#863C

Communication with encoder is faulty

 

16#004C

Configuration error at device

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#004D

The device driver needs a smaller servo clock.

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#004E

Error in internal communication with the device

Check the project for consistency and reload it into the controller.

16#863D

Communication to the device (drive or encoder) is faulty

 

16#0030

Value has an incorrect number format or is outside the valid number range

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online; acknowledge error with instruction "MC_Reset" and restart the command, if necessary

16#0055

The requested logical address is invalid.

  • Connect a suitable device.

  • Check the device (I/Os).

  • Check the topological configuration in HW Config.

  • Compare the configuration of HW Config and the technology object.

16#0056

The requested logical output address is invalid.

16#0057

The requested logical output address is invalid.

16#863E

Value of tag " ControlPanel.Input.TimeOut " is invalid (axis control panel)

 

16#0030

Value has an incorrect number format or is outside the valid number range

Correct the value in the variables of the technology object <Axis name>.ControlPanel.Input.TimeOut.

The value is specified in milliseconds (ms).

16#863F

Invalid value for the configuration date <Axis name>. Actor.DriveParameter.MaxSpeed

 

16#0030

Value has an incorrect number format or is outside the valid number range

Correct the reference value in the drive and in the configuration of the technology object to Actuator.MaxSpeed/2.

With analog drive connection, correct the reference value in the drive and in the configuration of the technology object to Actuator.MaxSpeed/1.17.

Configuration error of the command table

ErrorID

ErrorInfo

Description

Remedy

16#8700

Value for "Command type" in the command table is invalid

 

16#0001

-

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online and restart the command, if necessary

16#8701

Value for "Position / travel path" in the command table is invalid

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online and restart the command, if necessary

16#0005

Value is outside the number range (greater than 1E+12)

16#0006

Value is outside the number range (less than -1E+12)

16#8702

Value for "Velocity" in the command table is invalid

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online and restart the command, if necessary

16#0008

Value is greater than the configured maximum velocity

16#0009

Value is less than the configured start/stop velocity

16#8703

Value for "Duration" in the command table is invalid

 

16#0002

The value has an invalid number format

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online and restart the command, if necessary

16#0021

Value is greater than 64800 s

16#0022

Value is less than 0.001 s

16#8704

Value for "Next step" in the command table is invalid

 

16#0011

The selection value is invalid

  • Download error-free configuration to the controller; enable the axis again with instruction "MC_Power"

  • Correct the incorrect value online and restart the command, if necessary

16#0023

The command transition is not permitted for this command

Internal errors

ErrorID

ErrorInfo

Description

Remedy

16#8FFF

Internal error

 

16#F0**

-

POWER OFF and POWER ON the CPU

If this does not work, contact Customer Support. Have the following information ready:

  • ErrorID

  • ErrorInfo

  • Diagnostic buffer entries