The following table lists all ErrorIDs and ErrorInfos that can be indicated in Motion Control instructions. In addition to the cause of the error, remedies for eliminating the error are also listed.
Depending on the error reaction, the axis is stopped in the case of operating errors with stop of axis. The following error reactions are possible:
-
Remove enable
The setpoint 0 is output and the enable is removed. The axis is braked depending on the configuration in the drive, and is brought to a standstill.
-
Stop with emergency stop ramp
Active motion commands are aborted. The axis is braked with the emergency stop deceleration configured under "Technology object > Extended parameters > Dynamics > Emergency stop ramp" without any jerk limit and brought to a standstill.
Operating error with axis stop
|
ErrorID |
ErrorInfo |
Description |
Remedy |
Error reaction |
|---|---|---|---|---|
|
16#8000 |
Drive error, loss of "Drive ready" |
- |
||
|
16#0001 |
- |
Acknowledge error with instruction "MC_Reset"; provide drive signal; restart command, if necessary |
||
|
16#8001 |
SW low limit switch has been tripped |
- |
||
|
16#000E |
The position of the SW low limit switch was reached with the currently configured deceleration |
Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the SW limit switch |
||
|
16#000F |
The position of the SW low limit switch was reached with the emergency stop deceleration |
|||
|
16#0010 |
The position of the SW low limit switch was exceeded with the emergency stop deceleration |
Remove enable |
||
|
16#8002 |
SW high limit switch has been tripped |
- |
||
|
16#000E |
The position of the SW high limit switch was reached with the currently configured deceleration |
Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the SW limit switch |
||
|
16#000F |
The position of the SW high limit switch was reached with the emergency stop deceleration |
|||
|
16#0010 |
The position of the SW high limit switch was exceeded with the emergency stop deceleration |
Remove enable |
||
|
16#8003 |
HW low limit switch was reached |
For drive connection via PTO (Pulse Train Output): Stop with emergency stop ramp For drive connection via PROFIdrive/analog output: Remove enable |
||
|
16#000E |
The HW low limit switch was reached. The axis was stopped with the emergency stop deceleration. (The homing switch was not found during an active homing procedure) |
Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the HW limit switch. |
||
|
16#8004 |
HW high limit switch was reached |
For drive connection via PTO (Pulse Train Output): Stop with emergency stop ramp For drive connection via PROFIdrive/analog output: Remove enable |
||
|
16#000E |
The HW high limit switch was reached. The axis was stopped with the emergency stop deceleration. (The homing switch was not found during an active homing procedure) |
Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the HW limit switch. |
||
|
16#8005 |
PTO / HSC are already being used by another axis |
- |
||
|
16#0001 |
- |
The axis was configured incorrectly: Correct the configuration of the PTO (Pulse Train Output) / HSC (High Speed Counter) and download it to the controller |
||
|
More than one axis is to run with one PTO : Another axis is using the PTO / HSC. If the current axis is to assume the control, the other axis must be disabled with "MC_Power" Enable = FALSE. |
||||
|
16#8006 |
A communication error has occurred in the axis control panel |
Remove enable |
||
|
16#0012 |
A timeout has occurred. |
Check the cable connection and press the "Manual control" button again |
||
|
16#8007 |
The axis cannot be enabled |
- |
||
|
16#0025 |
Restarting |
Wait until the axis restart is complete. |
||
|
16#0026 |
Executing loading process in RUN mode |
Wait until the loading process is complete. |
||
|
16#8008 |
Invalid direction of motion |
- |
||
|
16#002E |
The selected motion direction is not allowed. |
|
||
|
16#002F |
A reversing motion is not possible with the selected motion direction. |
|||
|
16#8009 |
Reference switch/encoder zero mark not found |
Stop with emergency stop ramp |
||
|
16#0033 |
Error in the configuration, hardware or installation of the encoder or at the homing switch. |
|
||
|
16#800A |
Alarm message from encoder |
Remove enable |
||
|
16#0001 |
- |
Check the device with regard to function, connections and I/Os. |
||
|
16#0034 |
Hardware error at encoder |
|||
|
16#0035 |
Encoder dirty |
|||
|
16#0036 |
Error during reading of encoder absolute value |
Compare the encoder type in the drive or encoder parameter P979 with the configuration data of the technology object. |
||
|
16#0037 |
Zero mark monitoring of the encoder |
Encoder reports error in zero mark monitoring (fault code 0x0002 in Gx_XIST2, see PROFIdrive profile). Check the plant for electromagnetic compatibility (EMC). |
||
|
16#0038 |
Encoder is in "Parking" state |
|
||
|
16#0040 |
PROFIdrive: Encoder on bus failed (station failure). |
Check the device with regard to function, connections and I/Os. |
||
|
16#800B |
Range violation of the position |
Remove enable |
||
|
16#0039 |
Range violation in positive direction |
Home the axis to a valid actual value range. |
||
|
16#003A |
Range violation in negative direction |
|||
|
16#003B |
The change of the actual position in a position control clock cycle is longer than the length. |
Adjust the modulo length of the employed encoder. |
||
|
16#800C |
Alarm message from drive |
Remove enable |
||
|
16#0001 |
- |
Check the device with regard to function, connections and I/Os. In the "Tuning" dialog box, select a smaller gain (Kv). |
||
|
16#003C |
PROFIdrive: Drive signal "Control requested" failed. |
|||
|
16#003D |
PROFIdrive/analog drive connection: Drive has shut down. |
|||
|
16#003E |
PROFIdrive: Drive on bus failed (station failure) |
|||
|
16#800D |
The permitted following error was exceeded |
Remove enable |
||
|
16#0001 |
- |
|
||
|
16#800E |
Error at the hardware limit switch |
Remove enable |
||
|
16#0042 |
Illegal free travel direction with active hardware limit switch |
The programmed direction of movement is disabled due to the active hardware limit switch. Retract the axis in the opposite direction. |
||
|
16#0043 |
Hardware limit switch polarity is reversed, axis cannot be freed |
Check the mechanical configuration of the hardware limit switch. |
||
|
16#0044 |
Both hardware limit switches are active, axis cannot be freed |
|||
|
16#800F |
Error in target range |
Remove enable |
||
|
16#0045 |
Target range not reached |
Target range was not reached within the positioning tolerance time.
|
||
|
16#0046 |
Exit target range again |
The target range was exited within the minimum dwell time.
|
||
|
16#8010 |
Position of the SW low limit switch is greater than that of the SW high limit switch when the axis is not a modulo axis |
Remove enable |
||
|
16#0001 |
- |
Change the position of the software limit switches. |
||
Operating error without axis stop
|
ErrorID |
ErrorInfo |
Description |
Remedy |
|---|---|---|---|
|
16#8200 |
Axis is not enabled |
||
|
16#0001 |
- |
Enable the axis; restart the command |
|
|
16#8201 |
Axis has already been enabled by another " MC_Power " instance |
||
|
16#0001 |
- |
Enable the axis with only one "MC_Power" instance |
|
|
16#8202 |
The maximum number of simultaneous motion control commands has been exceeded (max. 200 commands for drive connection via PTO (Pulse Train Output) , max. 100 commands for drive connection via PROFIdrive /analog output) |
||
|
16#0001 |
- |
Reduce the number of simultaneously active commands; restart the command A command is active if parameter "Busy" = TRUE in the Motion Control instruction. |
|
|
16#8203 |
Axis is currently operated in "Manual control" (axis control panel) |
||
|
16#0001 |
- |
Exit "Manual control"; restart the command |
|
|
16#8204 |
Axis is not homed |
||
|
16#0001 |
- |
Home the axis with instruction "MC_Home"; restart the command |
|
|
16#8205 |
The axis is currently controlled by the user program (the error is only displayed in the axis control panel) |
||
|
16#0013 |
The axis is enabled in the user program |
Disable axis with instruction "MC_Power" and select "Manual control" again in the axis control panel |
|
|
16#8206 |
Technology object not activated yet |
||
|
16#0001 |
- |
Enable the axis with instruction "MC_Power" Enable = TRUE or enable the axis in the axis control panel. |
|
|
16#8207 |
Command rejected |
||
|
16#0016 |
Active homing is running; another homing method cannot be started. |
Wait for active homing to finish or abort the active homing with a motion command, for example, "MC_Halt". |
|
|
16#0018 |
The axis cannot be moved with a command table while it is being actively or passively homed. |
Wait until direct or passive homing is complete. |
|
|
16#0019 |
The axis cannot be actively or passively homed while a command table is being processed. |
Wait for command table to finish or abort the command table with a motion command, for example, "MC_Halt". |
|
|
16#0052 |
The specified position exceeds the numerical limit. |
Enter a valid position value at the Motion Control instruction. |
|
|
16#0053 |
The axis is ramping up. |
Wait until the axis is ready for operation. |
|
|
16#0054 |
Actual value is invalid |
To execute a "MC_Home" command, the actual values must be valid. Check the status of the actual values. The variable of the technology object <Axis name>."StatusSensor.State" must show the value 2 (valid). |
|
|
16#8208 |
Difference between maximum and start/stop velocity is invalid |
||
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
|
16#000A |
Value is less than or equal to 0. |
||
|
16#8209 |
Invalid acceleration for technology object "Axis" |
||
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
|
16#000A |
Value is less than or equal to 0. |
||
|
16#820A |
It is not possible to restart the axis |
||
|
16#0013 |
The axis is enabled in the user program |
Disable the axis with the "MC_Power" instruction; restart again |
|
|
16#0027 |
The axis is currently being operated in "Manual control" (axis control panel) |
Exit "Manual control"; restart again |
|
|
16#002C |
The axis is not disabled. |
Disable the axis; restart the command |
|
|
16#0047 |
The technology object is not ready for restart. |
Download the project again. |
|
|
16#0048 |
Condition for restart of the technology object is not satisfied. |
Disable the technology object. |
|
|
16#820B |
It is not possible to execute the command table |
||
|
16#0026 |
Executing loading process in RUN mode |
Wait until the loading process is complete. |
|
|
16#820C |
No configuration available |
||
|
16#0001 |
- |
Internal error Contact the hotline. |
|
Block parameter error
|
ErrorID |
ErrorInfo |
Description |
Remedy |
|---|---|---|---|
|
16#8400 |
Invalid value at parameter " Position " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#8401 |
Invalid value at parameter " Distance " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#8402 |
Invalid value at parameter " Velocity " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#0008 |
Value is greater than the configured maximum velocity |
||
|
16#0009 |
Value is less than the configured start/stop velocity |
||
|
16#0024 |
Value is less than 0 |
||
|
16#8403 |
Invalid value at parameter " Direction " of the Motion Control instruction |
||
|
|
16#0011 |
The selection value is invalid |
Correct the selection value; restart the command |
|
16#8404 |
Invalid value at parameter " Mode " of the Motion Control instruction |
||
|
|
16#0011 |
The selection value is invalid |
Correct the selection value; restart the command |
|
16#0015 |
Active/passive homing is not configured |
Correct the configuration and download it to the controller; enable the axis and restart the command |
|
|
16#0017 |
The direction reversal is activated at the hardware limit switch, despite the fact that the hardware limit switches are disabled |
|
|
|
16#0055 |
Invalid mode at incremental encoder |
Start a homing process for an incremental encoder using parameter "Mode" = 0, 1, 2, 3. |
|
|
16#0056 |
Invalid mode at absolute encoder |
Passive and active homing ("Mode" = 2, 3) are not possible for an absolute value encoder. Start a homing process for an absolute encoder using parameter "Mode" = 0, 1. |
|
|
16#8405 |
Invalid value at parameter " StopMode " of the Motion Control instruction |
||
|
|
16#0011 |
The selection value is invalid |
Correct the selection value; enable the axis again |
|
16#8406 |
Simultaneous forward and backward jogging is not allowed |
||
|
|
16#0001 |
- |
Take steps to ensure that parameters "JogForward" and "JogBackward" do not have signal status TRUE simultaneously; restart the command. |
|
16#8407 |
Switching to another axis with instruction " MC_Power " is only permitted after disabling the active axis. |
||
|
|
16#0001 |
- |
Disable the active axis; it is then possible to switch to the other axis and enable it. |
|
16#8408 |
Invalid value at parameter " Axis " of the Motion Control instruction |
||
|
|
16#001A |
The specified value does not match the required technology object version |
Correct the value; restart the command |
|
16#001B |
The specified value does not match the required technology object type |
||
|
16#001C |
The specified value is not a Motion Control technology data block |
||
|
16#8409 |
Invalid value at parameter " CommandTable " of the Motion Control instruction |
||
|
|
16#001A |
The specified value does not match the required technology object version |
Correct the value; restart the command |
|
16#001B |
The specified value does not match the required technology object type |
||
|
16#001C |
The specified value is not a Motion Control technology data block |
||
|
16#840A |
Invalid value at parameter " StartStep " of the Motion Control instruction |
||
|
|
16#000A |
Value is less than or equal to 0. |
Correct the value; restart the command |
|
16#001D |
The start step is greater than the end step |
||
|
16#001E |
Value is greater than 32 |
||
|
16#840B |
Invalid value at parameter " EndStep " of the Motion Control instruction |
||
|
|
16#000A |
Value is less than or equal to 0. |
Correct the value; restart the command |
|
16#001E |
Value is greater than 32 |
||
|
16#840C |
Invalid value at parameter " RampUpTime " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#0005 |
Value is outside the number range (greater than 1.0E12) |
||
|
16#000A |
Value is less than or equal to 0. |
||
|
16#840D |
Invalid value at parameter " RampDownTime " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#000A |
Value is less than or equal to 0. |
||
|
16#840E |
Invalid value at parameter " EmergencyRampTime " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#000A |
Value is less than or equal to 0. |
||
|
16#840F |
Invalid value at parameter " JerkTime " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#000A |
Value is less than or equal to 0. |
||
|
16#8410 |
Invalid value at parameter " Parameter " of the Motion Control instruction |
||
|
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
16#000B |
Address is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#0028 |
Data type of VARIANT pointer "Parameter" and "Value" do not match. |
Use a suitable data type; restart command |
|
|
16#0029 |
VARIANT pointer "Parameter" does not point to a data block of the technology object. |
Correct the VARIANT pointer; restart the command |
|
|
16#002A |
The value at the VARIANT pointer "Parameter" cannot be read. |
Correct the VARIANT pointer; restart the command |
|
|
16#002B |
The value at the VARIANT pointer "Parameter" cannot be written. |
Correct the VARIANT pointer or value; restart the command |
|
|
16#002C |
The axis is not disabled. |
Disable the axis; restart the command |
|
|
16#8411 |
Invalid value at parameter " Value " of the Motion Control instruction |
||
|
16#0002 |
The value has an invalid number format |
Correct the value; restart the command |
|
Configuration error of the axis
|
ErrorID |
ErrorInfo |
Description |
Remedy |
|---|---|---|---|
|
16#8600 |
Parameter assignment of pulse generator ( PTO is invalid |
||
|
|
16#000B |
The address is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#0014 |
The selected hardware is used by another application |
||
|
16#8601 |
Parameter assignment of the high-speed counter ( HSC ) is invalid |
||
|
|
16#000B |
The address is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#0014 |
The selected hardware is used by another application |
||
|
16#8602 |
Invalid parameter assignment of "Enable output" |
||
|
|
16#000B |
The address is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#8603 |
Invalid parameter assignment of "Ready input" |
||
|
|
16#000B |
The address is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#8604 |
Invalid "Pulses per motor revolution" value |
||
|
|
16#000A |
Value is less than or equal to 0 |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#8605 |
Invalid "Distance per revolution" value |
||
|
|
16#0002 |
The value has an invalid number format |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#000A |
Value is less than or equal to 0 |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8606 |
Invalid "Start/stop velocity" value |
||
|
|
16#0002 |
The value has an invalid number format |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#0003 |
Value is higher than the hardware high limit |
||
|
16#0004 |
Value is lower than the hardware low limit |
||
|
16#0007 |
The start/stop velocity is greater than the maximum velocity |
||
|
16#8607 |
Invalid "maximum velocity" value |
||
|
|
16#0002 |
The value has an invalid number format |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#0003 |
Value is higher than the hardware high limit |
||
|
16#0004 |
Value is lower than the hardware low limit |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8608 |
Invalid "Acceleration" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0003 |
Value is higher than the hardware high limit |
||
|
16#0004 |
Value is lower than the hardware low limit |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8609 |
Invalid "Deceleration" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0003 |
Value is higher than the hardware high limit |
||
|
16#0004 |
Value is lower than the hardware low limit |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#860A |
Invalid "Emergency stop deceleration" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0003 |
Value is higher than the hardware high limit |
||
|
16#0004 |
Value is lower than the hardware low limit |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#860B |
Value for position of the SW low limit switch is invalid |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#0030 |
The position value of the software low limit switch is greater than that of the software high limit switch |
||
|
16#860C |
Value for position of the SW high limit switch is invalid |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#860D |
Invalid address of the HW low limit switch |
||
|
|
16#000B |
Invalid address |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#000C |
The address of the falling edge is invalid |
||
|
16#000D |
The address of the rising edge is invalid |
||
|
16#860E |
Invalid address of the HW high limit switch |
||
|
|
16#000B |
Invalid address |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#000C |
The address of the falling edge is invalid |
||
|
16#000D |
The address of the rising edge is invalid |
||
|
16#860F |
Invalid "home position offset" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8610 |
Invalid "approach velocity" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0008 |
The velocity is greater than the maximum velocity |
||
|
16#0009 |
The velocity is less than the start/stop velocity |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8611 |
Invalid "Homing velocity" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0008 |
The velocity is greater than the maximum velocity |
||
|
16#0009 |
The velocity is less than the start/stop velocity |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8612 |
Invalid address of the homing switch |
||
|
|
16#000B |
Invalid address |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#000C |
The address of the falling edge is invalid |
||
|
16#000D |
The address of the rising edge is invalid |
||
|
16#8613 |
During active homing, direction reversal at the hardware limit switch is activated although the hardware limit switches are not configured |
||
|
|
16#0001 |
- |
|
|
16#8614 |
Invalid "Jerk" value |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#001F |
Value is greater than the maximum jerk |
||
|
16#0020 |
Value is less than the minimum jerk |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8615 |
Value for "Unit of measurement" is invalid |
||
|
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
16#8616 |
Address of homing switch is invalid (passive homing as of V4) |
||
|
16#0011 |
The selection value is invalid |
|
|
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8617 |
Value of tag <Axis name>. Sensor.Sensor[1].ActiveHoming.Mode is invalid |
||
|
16#0011 |
The selection value is invalid (Valid value: 2 = Homing via digital input) |
|
|
|
16#8618 |
Value of tag <Axis name>. Sensor.Sensor[1].PassiveHoming.Mode is invalid |
||
|
16#0011 |
The selection value is invalid (Valid value: 2 = Homing via digital input) |
|
|
|
16#8619 |
Value of tag <Axis name>. Actor.Type is invalid |
||
|
16#0011 |
The selection value is invalid (Valid value: 2 = Connection via pulse interface) |
|
|
|
16#861A |
Value for "Permitted direction of rotation" is invalid |
||
|
16#0011 |
The selection value is invalid |
|
|
|
16#002D |
"Both directions" not permitted with direction output switched off |
||
|
16#861B |
Faulty load gear factors |
||
|
16#0031 |
Valid is invalid. |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#861C |
Illegal combination of data for homing with incremental encoder |
||
|
16#0031 |
Valid is invalid. |
|
|
|
16#861D |
The set encoder mounting type is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].MountingMode |
||
|
16#0011 |
The selection value is invalid |
|
|
|
16#861E |
The configuration of the measuring wheel circumference of the encoder is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.DistancePerRevolution |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#861F |
The configuration for the resolution of the linear encoder is faulty. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.Resolution |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8620 |
The configured fine resolution for Gx_XIST1 is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist1 |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8621 |
The set fine resolution for Gx_XIST1 in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist1 is not consistent with the setting in PROFIdrive parameter P979 |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8622 |
Invalid value for the configuration date <Axis name>. Actor.Interface.AddressIn or <Axis name>. Actor.Interface.AddressOut |
||
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#8623 |
The value set in the tag <axis name>. Sensor.Sensor[1].Type is invalid. |
||
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#8624 |
The set encoder system is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].System |
||
|
16#0011 |
The selection value is invalid |
|
|
|
16#8625 |
Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.MinDwellTime |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8626 |
Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.Window |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8627 |
The configuration of the PROFIdrive interface of the actual value is faulty. Invalid value in <Axis name>. Sensor.Sensor[1].Interface.AddressIn or <Axis name>. Sensor.Sensor[1].Interface.AddressOut |
||
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#8628 |
Faulty controller factors |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
The value for the gain or the precontrol of the control loop is faulty.
|
|
|
16#8629 |
Limit for standstill signal is faulty. Invalid value in <Axis name>. StandStillSignal.VelocityThreshold |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#862A |
Parameter of position monitoring is faulty. Invalid value in <Axis name>. PositioningMonitoring.ToleranceTime |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#862B |
Inconsistent PROFIBUS parameterization; the sum of Ti and To is greater than one DP cycle |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#862C |
Parameter of standstill monitoring is faulty. Invalid value in <Axis name>. StandStillSignal.MinDwellTime |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#862D |
Parameter of following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MinValue |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#862E |
Invalid value for the configuration date <Axis name>. Modulo.Length |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#862F |
Invalid value for the configuration date <Axis name>. Modulo.StartValue |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8630 |
Invalid value for the configuration date <Axis name>. Actor.DriveParameter.ReferenceSpeed |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8631 |
The set fine resolution for Gx_XIST2 is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.FineResolutionXist2 |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8632 |
The number of determinable encoder revolutions is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].Parameter.DeterminableRevolutions |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8633 |
The specified approach direction of the homing switch for passive homing is invalid. Invalid value in <Axis name>. Sensor.Sensor[1].PassiveHoming.Direction |
||
|
16#8634 |
Parameter of the following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MaxValue |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8635 |
Parameter of the following error monitoring is faulty. Invalid value in <Axis name>. FollowingError.MinVelocity |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8636 |
Controller factor is incorrect. Invalid value of the precontrol factor <Axis name>. PositionControl.Kpc |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#8637 |
Invalid value for the configuration date <Axis name>. Sensor.Sensor[1].Interface.Type |
||
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#8638 |
Invalid value for the configuration date <Axis name>. Sensor.Sensor[1].Interface.HSC |
||
|
16#0011 |
The selection value is invalid |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#8639 |
Error at the drive |
||
|
16#0049 |
Configuration error at device |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#004A |
The technology needs a smaller servo clock. |
Internal system error. Check the project for consistency and reload it into the controller. |
|
|
16#004B |
Device driver not initialized during ramp-up. |
To enable a technology object, the actuator driver must be initialized. Execute the command again later. |
|
|
16#863A |
Communication to the drive is faulty |
||
|
16#004C |
Configuration error at device |
|
|
|
16#004D |
The device driver needs a smaller servo clock. |
|
|
|
16#004E |
Error in internal communication with the device |
Check the project for consistency and reload it into the controller. |
|
|
16#863B |
Error at encoder |
||
|
16#0049 |
Configuration error at device |
Download error-free configuration to the controller; enable the axis again with instruction "MC_Power" |
|
|
16#004A |
The technology needs a smaller servo clock. |
Internal system error. Check the project for consistency and reload it into the controller. |
|
|
16#004B |
Device driver not initialized during ramp-up. |
To enable a technology object, the actuator driver must be initialized. Execute the command again later. |
|
|
16#863C |
Communication with encoder is faulty |
||
|
16#004C |
Configuration error at device |
|
|
|
16#004D |
The device driver needs a smaller servo clock. |
|
|
|
16#004E |
Error in internal communication with the device |
Check the project for consistency and reload it into the controller. |
|
|
16#863D |
Communication to the device (drive or encoder) is faulty |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
|
|
|
16#0055 |
The requested logical address is invalid. |
|
|
|
16#0056 |
The requested logical output address is invalid. |
||
|
16#0057 |
The requested logical output address is invalid. |
||
|
16#863E |
Value of tag " ControlPanel.Input.TimeOut " is invalid (axis control panel) |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
Correct the value in the variables of the technology object <Axis name>.ControlPanel.Input.TimeOut. The value is specified in milliseconds (ms). |
|
|
16#863F |
Invalid value for the configuration date <Axis name>. Actor.DriveParameter.MaxSpeed |
||
|
16#0030 |
Value has an incorrect number format or is outside the valid number range |
Correct the reference value in the drive and in the configuration of the technology object to Actuator.MaxSpeed/2. With analog drive connection, correct the reference value in the drive and in the configuration of the technology object to Actuator.MaxSpeed/1.17. |
|
Configuration error of the command table
|
ErrorID |
ErrorInfo |
Description |
Remedy |
|---|---|---|---|
|
16#8700 |
Value for "Command type" in the command table is invalid |
||
|
|
16#0001 |
- |
|
|
16#8701 |
Value for "Position / travel path" in the command table is invalid |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0005 |
Value is outside the number range (greater than 1E+12) |
||
|
16#0006 |
Value is outside the number range (less than -1E+12) |
||
|
16#8702 |
Value for "Velocity" in the command table is invalid |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0008 |
Value is greater than the configured maximum velocity |
||
|
16#0009 |
Value is less than the configured start/stop velocity |
||
|
16#8703 |
Value for "Duration" in the command table is invalid |
||
|
|
16#0002 |
The value has an invalid number format |
|
|
16#0021 |
Value is greater than 64800 s |
||
|
16#0022 |
Value is less than 0.001 s |
||
|
16#8704 |
Value for "Next step" in the command table is invalid |
||
|
|
16#0011 |
The selection value is invalid |
|
|
16#0023 |
The command transition is not permitted for this command |
||
Internal errors
|
ErrorID |
ErrorInfo |
Description |
Remedy |
|---|---|---|---|
|
16#8FFF |
Internal error |
||
|
|
16#F0** |
- |
POWER OFF and POWER ON the CPU If this does not work, contact Customer Support. Have the following information ready:
|
See also
Error displays of the Motion Control statements (S7-1200)
Tags of the positioning axis technology object V4...5 (S7-1200)
ErrorIDs and ErrorInfos (S7-1200)
Using multiple axes with the same PTO (S7-1200)
Using multiple drives with the same PTO (S7-1200)
Tracking jobs from higher priority classes (execution levels) (S7-1200)
Special cases when using software limit switches for drive connection via PTO (S7-1200)