ErrorIDs 16#8000-16#8013 (S7-1200) - Motion Control

Using S7-1200 Motion Control (S7-1200)

ft:publication_title
Using S7-1200 Motion Control (S7-1200)
Product
Motion Control
Version
V21
Publication date
11/2025
Language
en-US
ErrorIDs 16#8000-16#8013

Operating error with axis stop

ErrorID

ErrorInfo

Description

Remedy

Error reaction

16#8000

Drive error, loss of "Drive ready"

-

16#0001

-

Acknowledge error with instruction "MC_Reset"; provide drive signal; restart command, if necessary

 

16#8001

Low SW limit switch has been tripped

-

16#000E

The position of the low SW limit switch was reached with the currently configured deceleration

Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the SW limit switch

16#000F

The position of the low SW limit switch was reached with the emergency deceleration

16#0010

The position of the low SW limit switch was exceeded with the emergency deceleration

Remove enable

16#8002

High SW limit switch has been triggered

-

16#000E

The position of the high SW limit switch was reached with the currently configured deceleration

Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the SW limit switch

16#000F

The position of the high SW limit switch was reached with the emergency deceleration

16#0010

The position of the high SW limit switch was exceeded with the emergency deceleration

Remove enable

16#8003

Low HW limit switch has been approached

For drive connection via PTO (Pulse Train Output):

Stop with emergency stop ramp

For drive connection via PROFIdrive/analog output:

Remove enable

16#000E

Low HW limit switch has been approached. The axis was stopped with the emergency deceleration.

(During an active homing procedure, the homing switch was not found)

Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the HW limit switch.

16#8004

High HW limit switch has been approached

For drive connection via PTO (Pulse Train Output):

Stop with emergency stop ramp

For drive connection via PROFIdrive/analog output:

Remove enable

16#000E

High HW limit switch has been approached. The axis was stopped with the emergency deceleration.

(During an active homing procedure, the homing switch was not found)

Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the HW limit switch.

16#8005

PTO / HSC are already being used by another axis

-

16#0001

-

The axis was configured incorrectly:

Correct the configuration of the PTO (Pulse Train Output) / HSC (High Speed Counter) and download it to the controller

More than one axis is to run with one PTO :

Another axis is using the PTO / HSC. If the current axis is to assume the control, the other axis must be disabled with "MC_Power" Enable = FALSE.
(See also "Using multiple axes with the same PTO")

16#8006

A communication error occurred in the axis control panel

Remove enable

16#0012

A timeout has occurred

Check the cable connection and press the "Manual control" button again

16#8007

It is not possible to enable the axis

-

16#0025

Restarting

Wait until the axis restart is complete.

16#0026

Executing loading process in RUN mode

Wait until the loading process is complete.

16#8008

Invalid direction of movement

-

 

16#002E

The selected motion direction is not allowed.

  • Adjust the motion direction and restart the command.

  • Adjust the allowed direction of rotation in the technology object configuration under "Extended parameters > Mechanics". Restart the job.

16#002F

A reversing motion is not possible with the selected motion direction.

16#8009

Reference switch/encoder zero mark not found

Stop with emergency stop ramp

 

16#0033

Error in the configuration, hardware or mounting of the encoder or at the homing switch.

  • Connect a suitable device.

  • Check the device (I/Os).

  • Compare the configuration of HW Config and the technology object.

16#800A

Alarm message from encoder

Remove enable

 

16#0001

-

Check the device with regard to function, connections and I/Os.

16#0034

Hardware error at encoder

16#0035

Encoder dirty

16#0036

Error reading the encoder absolute value

Compare the encoder type in the drive or encoder parameter P979 with the configuration data of the technology object.

16#0037

Zero mark monitoring of the encoder

Encoder reports error in zero mark monitoring (fault code 0x0002 in Gx_XIST2, see PROFIdrive profile).

Check the plant for electromagnetic compatibility (EMC).

16#0038

Encoder has gone in parking state

  • Search for the cause of the error in the connected drive or encoder.

  • Check whether the error message was possibly triggered by a commissioning action at the drive or encoder.

16#0040

PROFIdrive: Encoder on bus failed (station failure).

Check the device with regard to function, connections and I/Os.

16#800B

Range violation of the position

Remove enable

 

16#0039

Range violation in positive direction

Home the axis to a valid actual value range.

16#003A

Range violation in negative direction

16#003B

The change of the actual position in a position control clock cycle is longer than the length.

Adjust the modulo length of the employed encoder.

16#800C

Alarm message from drive

Remove enable

 

16#0001

-

Check the device with regard to function, connections and I/Os.

In the "Tuning" dialog box, select a smaller gain (Kv).

16#003C

PROFIdrive: Drive signal "Control requested" failed.

16#003D

PROFIdrive/analog drive connection: Drive has shut down.

16#003E

PROFIdrive: Drive on bus failed (station failure)

16#800D

The permitted following error has been exceeded

Remove enable

 

16#0001

-

  • Check the configuration of the control loop.

  • Check the direction signal of the encoder.

  • Check the configuration of following error monitoring.

16#800E

Error at HW limit switch

Remove enable

 

16#0042

Illegal free travel direction with active hardware limit switch

The programmed direction of movement is disabled due to the active hardware limit switch.

Retract the axis in the opposite direction.

16#0043

HW limit switch polarity reversed, free travel not possible.

Check the mechanical configuration of the hardware limit switch.

16#0044

Both hardware limit switches are enabled, no free travel

16#800F

Error in target range

Remove enable

 

16#0045

Target range not reached

Target range was not reached within the positioning tolerance time.

  • Check the configuration of the position monitoring.

  • Check the configuration of the control loop.

16#0046

Exit target range again

The target range was exited within the minimum dwell time.

  • Check the configuration of the position monitoring.

  • Check the configuration of the control loop.

16#8010

Position of the low SW limit switch is greater than the position of the high SW limit switch when the axis is not a modulo axis.

Remove enable

 

16#0001

-

Change the position of the software limit switches.

16#8011

Approach velocity to the homing switch / zero mark equals zero.

Remove enable

 

16#000A

Value is less than or equal to 0.

Approach velocity > Select zero

16#8012

Homing velocity for setting the home position equals zero.

Remove enable

 

16#000A

Value is less than or equal to 0.

Homing velocity > Select zero

16#8013

The axis cannot occupy the PTO because it is being used by "CTRL_PTO".

Remove enable

 

16#0001

-

Select another PTO in the configuration.