Operating error with axis stop
|
ErrorID |
ErrorInfo |
Description |
Remedy |
Error reaction |
|---|---|---|---|---|
|
16#8000 |
Drive error, loss of "Drive ready" |
- |
||
|
16#0001 |
- |
Acknowledge error with instruction "MC_Reset"; provide drive signal; restart command, if necessary |
||
|
16#8001 |
Low SW limit switch has been tripped |
- |
||
|
16#000E |
The position of the low SW limit switch was reached with the currently configured deceleration |
Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the SW limit switch |
||
|
16#000F |
The position of the low SW limit switch was reached with the emergency deceleration |
|||
|
16#0010 |
The position of the low SW limit switch was exceeded with the emergency deceleration |
Remove enable |
||
|
16#8002 |
High SW limit switch has been triggered |
- |
||
|
16#000E |
The position of the high SW limit switch was reached with the currently configured deceleration |
Acknowledge the error with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the SW limit switch |
||
|
16#000F |
The position of the high SW limit switch was reached with the emergency deceleration |
|||
|
16#0010 |
The position of the high SW limit switch was exceeded with the emergency deceleration |
Remove enable |
||
|
16#8003 |
Low HW limit switch has been approached |
For drive connection via PTO (Pulse Train Output): Stop with emergency stop ramp For drive connection via PROFIdrive/analog output: Remove enable |
||
|
16#000E |
Low HW limit switch has been approached. The axis was stopped with the emergency deceleration. (During an active homing procedure, the homing switch was not found) |
Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the positive direction out of the range of the HW limit switch. |
||
|
16#8004 |
High HW limit switch has been approached |
For drive connection via PTO (Pulse Train Output): Stop with emergency stop ramp For drive connection via PROFIdrive/analog output: Remove enable |
||
|
16#000E |
High HW limit switch has been approached. The axis was stopped with the emergency deceleration. (During an active homing procedure, the homing switch was not found) |
Acknowledge the error for an enabled axis with instruction "MC_Reset"; use a motion command to move the axis in the negative direction out of the range of the HW limit switch. |
||
|
16#8005 |
PTO / HSC are already being used by another axis |
- |
||
|
16#0001 |
- |
The axis was configured incorrectly: Correct the configuration of the PTO (Pulse Train Output) / HSC (High Speed Counter) and download it to the controller |
||
|
More than one axis is to run with one PTO : Another axis is using the PTO / HSC. If the current axis is to assume the control, the other axis must be disabled with "MC_Power" Enable = FALSE. |
||||
|
16#8006 |
A communication error occurred in the axis control panel |
Remove enable |
||
|
16#0012 |
A timeout has occurred |
Check the cable connection and press the "Manual control" button again |
||
|
16#8007 |
It is not possible to enable the axis |
- |
||
|
16#0025 |
Restarting |
Wait until the axis restart is complete. |
||
|
16#0026 |
Executing loading process in RUN mode |
Wait until the loading process is complete. |
||
|
16#8008 |
Invalid direction of movement |
- |
||
|
16#002E |
The selected motion direction is not allowed. |
|
||
|
16#002F |
A reversing motion is not possible with the selected motion direction. |
|||
|
16#8009 |
Reference switch/encoder zero mark not found |
Stop with emergency stop ramp |
||
|
16#0033 |
Error in the configuration, hardware or mounting of the encoder or at the homing switch. |
|
||
|
16#800A |
Alarm message from encoder |
Remove enable |
||
|
16#0001 |
- |
Check the device with regard to function, connections and I/Os. |
||
|
16#0034 |
Hardware error at encoder |
|||
|
16#0035 |
Encoder dirty |
|||
|
16#0036 |
Error reading the encoder absolute value |
Compare the encoder type in the drive or encoder parameter P979 with the configuration data of the technology object. |
||
|
16#0037 |
Zero mark monitoring of the encoder |
Encoder reports error in zero mark monitoring (fault code 0x0002 in Gx_XIST2, see PROFIdrive profile). Check the plant for electromagnetic compatibility (EMC). |
||
|
16#0038 |
Encoder has gone in parking state |
|
||
|
16#0040 |
PROFIdrive: Encoder on bus failed (station failure). |
Check the device with regard to function, connections and I/Os. |
||
|
16#800B |
Range violation of the position |
Remove enable |
||
|
16#0039 |
Range violation in positive direction |
Home the axis to a valid actual value range. |
||
|
16#003A |
Range violation in negative direction |
|||
|
16#003B |
The change of the actual position in a position control clock cycle is longer than the length. |
Adjust the modulo length of the employed encoder. |
||
|
16#800C |
Alarm message from drive |
Remove enable |
||
|
16#0001 |
- |
Check the device with regard to function, connections and I/Os. In the "Tuning" dialog box, select a smaller gain (Kv). |
||
|
16#003C |
PROFIdrive: Drive signal "Control requested" failed. |
|||
|
16#003D |
PROFIdrive/analog drive connection: Drive has shut down. |
|||
|
16#003E |
PROFIdrive: Drive on bus failed (station failure) |
|||
|
16#800D |
The permitted following error has been exceeded |
Remove enable |
||
|
16#0001 |
- |
|
||
|
16#800E |
Error at HW limit switch |
Remove enable |
||
|
16#0042 |
Illegal free travel direction with active hardware limit switch |
The programmed direction of movement is disabled due to the active hardware limit switch. Retract the axis in the opposite direction. |
||
|
16#0043 |
HW limit switch polarity reversed, free travel not possible. |
Check the mechanical configuration of the hardware limit switch. |
||
|
16#0044 |
Both hardware limit switches are enabled, no free travel |
|||
|
16#800F |
Error in target range |
Remove enable |
||
|
16#0045 |
Target range not reached |
Target range was not reached within the positioning tolerance time.
|
||
|
16#0046 |
Exit target range again |
The target range was exited within the minimum dwell time.
|
||
|
16#8010 |
Position of the low SW limit switch is greater than the position of the high SW limit switch when the axis is not a modulo axis. |
Remove enable |
||
|
16#0001 |
- |
Change the position of the software limit switches. |
||
|
16#8011 |
Approach velocity to the homing switch / zero mark equals zero. |
Remove enable |
||
|
16#000A |
Value is less than or equal to 0. |
Approach velocity > Select zero |
||
|
16#8012 |
Homing velocity for setting the home position equals zero. |
Remove enable |
||
|
16#000A |
Value is less than or equal to 0. |
Homing velocity > Select zero |
||
|
16#8013 |
The axis cannot occupy the PTO because it is being used by "CTRL_PTO". |
Remove enable |
||
|
16#0001 |
- |
Select another PTO in the configuration. |
||