Using IEC timers and counters (S7-1200, S7-1500) - STEP 7

Programming recommendations (S7-1200, S7-1500)

ft:publication_title
Programming recommendations (S7-1200, S7-1500)
Product
STEP 7
Version
V21
Publication date
11/2025
Language
en-US
Using IEC timers and counters

Advantages of IEC timers and counters

The universal use of IEC timers and counters makes your program code more efficient.

This gives you the following advantages:

  • The blocks can be called multiple times with newly generated instance data blocks.

  • The IEC counters have a large counting range.

  • Compared to S5 timers, IEC timers have better performance and greater time accuracy.

Programming in STEP 7 V5.x

The S5 timers and counters in STEP 7 V5.x were addressed absolutely via a number. Due to this dependency on numbers, program blocks were not reusable with S5 timers and counters.

The value range of a timer was limited to 9990 seconds and that of a counter limited to a maximum of 999.

Procedure in STEP 7 TIA Portal

You declare IEC timers and counters in the program block where they are called or needed. The IEC timer is a structure of data type IEC_TIMER, IEC_LTIMER, or TON_TIME and TON_LTIME, for example, which you can also declare as a local tag in a block. The IEC counter is a structure of data type IEC_SCOUNTER, IEC_USCOUNTER, etc.

Programming examples in the TIA Portal

The following example shows you how to declare an IEC timer and IEC counter as a local tag:

The data of the TON IEC timer and the CTU IEC counter is stored as a local tag (multi-instance) in the block interface.​

You also have the option to create IEC timers and IEC counters within structures as multiple instances and to use them in your program code.

  1. To do this, for example, create a global data block with an ARRAY of TON. The data type TON does not appear in the drop-down list, but can be entered manually:

  2. Create a function block and drag the instruction "TON: Generate on-delay" to a network. Call the instance of IEC timer TON as follows:

Call of a timer as multi-instance

If you want to use the IN parameter to start a timer as multi-instance, you must not initialize it beforehand in your program code. In this case, the timer called at the IN parameter no longer recognizes a positive signal edge and the timer is not started:

1. Create the timer "Time_1" as a multi-instance of the data type "TP_TIME" in the "Static" section of the block interface.

2. Write the following program code:

STL Copies the following program code to clipboard.

Explanation

A "Tag_Output"

// When the "Tag_Output" output receives the signal state 1,

= #​Time_1.IN

// the IN parameter of the multi-instance timer #Timer_1 is initialized with a positive signal edge.

CALL #Time_1

// When the multi-instance timer is now called and the IN parameter queried again, the timer is not started because there is no new positive signal edge.

// Enter TIME as data type of the instruction.

time_type := Time

IN := "Tag_Output"

PT := T#30s

Q := "Tag_4"

ET := "Tag_ElapsedTime"

This is why you must program the initialization of the multi-instance timer within the call.

STL Copies the following program code to clipboard.

Explanation

CALL #Time_1

// The timer is called and started.

// Enter TIME as data type of the instruction.

time_type := Time

IN := "Tag_Output"

PT := T#30s

Q := "Tag_4"

ET := "Tag_ElapsedTime"