Control mode as of V2 (S7-1200, S7-1500) - PID

Using PID_Compact (S7-1200, S7-1500)

ft:publication_title
Using PID_Compact (S7-1200, S7-1500)
Product
PID
Version
V20
Publication date
11/2024
Language
en-US
Control mode as of V2

Physical quantity

Select the unit of measurement and physical quantity for the setpoint and the process value in the "Controller type" group. The setpoint and the process value are displayed in this unit.

Control logic

An increase of the output value is generally intended to cause an increase in the process value. This is referred to as a normal control logic.

PID_Compact does not work with negative proportional gain. Select the check box "Invert control logic" to reduce the process value with a higher output value.

Examples

  • Opening the drain valve will reduce the level of a container's contents.

  • Increasing cooling will reduce the temperature.

Startup characteristics

  1. To switch to "Inactive" mode after CPU restart, clear the "Activate Mode after CPU restart" check box.

    To switch to the operating mode saved in the Mode parameter after CPU restart, select the "Activate Mode after CPU restart" check box.

  2. In the "Set Mode to" drop-down list, select the mode that is to be enabled after a complete download to the device.

    After a complete download to the device, PID_Compact starts in the selected operating mode. With each additional restart, PID_Compact starts in the mode that was last saved in Mode.

Example

You have selected the "Activate Mode after CPU restart" check box and the entry "Pretuning" in the "Set Mode to" list. After a complete download to the device, PID_Compact starts in the "Pretuning" mode. If pretuning is still active, PID_Compact starts in "Pretuning" mode again after restart of the CPU. If pretuning was successfully completed and automatic mode is active, PID_Compact starts in "Automatic mode" after restart of the CPU.