Description
The instruction "Time accumulator" is used to accumulate time values within a period set by the parameter PT. When the signal state at the IN parameter changes to "1", the time measurement is executed and the time PT is started. While the time duration PT is running, the time values that are recorded when the IN parameter has signal state "1" are accumulated. If the signal state at the "IN" input changes to "0", the time measurement is interrupted. If the signal state at the "IN" input changes back to "1", the time measurement is restarted. The accumulated time is output in the ET parameter and can be queried there. When the time duration PT is reached, the Q parameter has signal state "1". The Q parameter remains set to "1", even when the signal state at the IN parameter changes to "0".
The R parameter resets the ET and Q parameters regardless of the signal state at the IN parameter.
Each call of the "Time accumulator" instruction must be assigned an IEC timer in which the instance data is stored.
For information on calling IEC timers within structures (multi-instance), please refer to: Calling IEC timers
For CPUs of the S7-1200 series
An IEC Timer is a structure of the data type IEC_TIMER or TONR_TIME that you can declare as follows:
-
Declaration of an instance data block of system data type IEC_TIMER (for example, "MyIEC_TIMER_DB")
-
Declaration as local tag of the data type TONR_TIME in the "Static" section of a program block (for example, #MyIEC_TIMER_Instance)
For CPUs of the S7-1500 series
An IEC Timer is a structure of the data type IEC_TIMER, IEC_LTIMER, TONR_TIME or TONR_LTIME that you can declare as follows:
-
Declaration of an instance data block of system data type IEC_TIMER or IEC_LTIMER (for example, "MyIEC_TIMER_DB")
-
Declaration as local tag of the data type TONR_TIME or TONR_LTIME in the "Static" section of a program block (for example, #MyIEC_TIMER_Instance)
IEC timer as instance data block of system data type IEC_<Timer> (Shared DB)
You can declare the IEC timer as a data block as follows:
<IEC_Timer_DB>.TONR();
IEC timer as local tag from the block interface (multi-instance)
You can declare the IEC timer as a local tag as follows:
#myLocal_Timer();
Updating the actual values in the instance data
The instance data from "Time accumulator" is updated according to the following rules:
-
IN input
The "Time accumulator" instruction compares the current RLO with the RLO from the previous query, which is saved in the IN parameter in the instance data. If the instruction detects a change in the RLO from "0" to "1", there is a positive signal edge and the time measurement is continued. If the instruction in the RLO detects a change from "1" to "0", there is a negative signal edge and the time measurement is interrupted. After the "Time accumulator" instruction has been processed, the value of the IN parameter is updated in the instance data and is used as edge memory bit for the next query.
Note that the edge evaluation is disrupted when the actual values of the IN parameter are written or initialized by other functions.
-
PT input
The value at the PT input is written to the PT parameter in the instance data when the edge changes at the IN input.
-
R input
The signal "1" at input R resets the time measurement and blocks it. Edges at the IN input are ignored. The signal "0" at input R enables time measurement again.
Note
Initialize parameter R
In order to initialize parameter R, you have to define a tag which you interconnect and then initialize in the "Time accumulator" instruction.
Example:
#IEC_Timer_0_Instance(IN:=#Start,R:=#Reset,PT:=_time_in_,Q=>_bool_out_,ET=>_time_out);#Reset := TRUE; -
Q and ET outputs
The actual values of the Q and ET outputs are updated in the following cases:
-
When the instruction is called, if the ET or Q outputs are interconnected.
Or
-
At an access to Q or ET.
If the outputs are not interconnected and also not queried, the current time value at the Q and ET outputs is not updated. The outputs are not updated, even if the instruction is skipped in the program.
The internal parameters of the "Time accumulator" instruction are used to calculate the time values for Q and ET. Note that the time measurement is disrupted when the actual values of the instruction are written or initialized by other functions.
-
|
|
Danger |
|
Danger when reinitializing the actual values Reinitializing the actual values of an IEC timer while the time measurement is running disrupts the function of the IEC timer. Changing the actual values can result in inconsistencies between the program and the actual process. This can cause serious damage to property and personal injury. The following functions can cause the actual values to be reinitialized:
Before you execute these functions, take the following precautions:
|
|
Parameters
The following table shows the parameters of the instruction:
|
Parameters |
Declaration |
Data type |
Memory area |
Description |
|
|---|---|---|---|---|---|
|
S7-1200 |
S7-1500 |
||||
|
IN |
Input |
BOOL |
BOOL |
I, Q, M, D, L, P |
Start input |
|
R |
Input |
BOOL |
BOOL |
I, Q, M, D, L, P |
Reset of the ET and Q parameters |
|
PT |
Input |
TIME |
TIME, LTIME |
I, Q, M, D, L, P |
Maximum duration of time recording. The value of the PT parameter must be positive. |
|
Q |
Output |
BOOL |
BOOL |
I, Q, M, D, L, P |
Operand that remains set when the timer PT has expired. |
|
ET |
Output |
TIME |
TIME, LTIME |
I, Q, M, D, L, P |
Accumulated time |
Pulse timing diagram
The following figure shows the pulse timing diagram of the "Time accumulator" instruction:
Example
The following example shows how the instruction works:
|
"TONR_DB".TONR(IN := "Tag_Start", R := "Tag_Reset", PT := "Tag_PresetTime", Q => "Tag_Status", ET => "Tag_Time"); |
When the signal state of the "Tag_Start" operand changes from "0" to "1", the time programmed for the PT parameter is started. While the time is running, the time values are accumulated that are recorded when the "Tag_Start" operand has signal state "1". The accumulated time is stored in the "Tag_Time" operand. When the time value specified for the PT parameter is reached, the "Tag_Status" operand is set to the signal state "1". The current time value is stored in the "Tag_Time" operand.