MCAT: Motor control-timer alarm

Description

The "Motor control-timer alarm" instruction is used to accumulate the time from the point at which one of the command inputs (opening or closing) is switched on. The time is accumulated until the preset time is exceeded or the relevant feedback input indicates that the device has executed the requested operation within the specified time. If the preset time is exceeded before the feedback is received, the corresponding alarm is triggered.

The "Motor control-timer alarm" instruction returns no error information.

Parameters

The following table shows the parameters of the "Motor control-timer alarm" instruction:

Parameters

Declaration

Data type

Memory space

Description

EN

Input

BOOL

I, Q, M, D, L, T, C or constant

Enable input

ENO

Output

BOOL

I, Q, M, D, L

Enable output

O_CMD

Input

BOOL

I, Q, M, D, L or constant

"Open" command input

C_CMD

Input

BOOL

I, Q, M, D, L or constant

"Close" command input

S_CMD

Input

BOOL

I, Q, M, D, L or constant

"Stop" command input

O_FB

Input

BOOL

I, Q, M, D, L or constant

Feedback input when opening

C_FB

Input

BOOL

I, Q, M, D, L or constant

Feedback input when closing

OO

Output

BOOL

I, Q, M, D, L

"Open" output

CO

Output

BOOL

I, Q, M, D, L

"Close" output

OA

Output

BOOL

I, Q, M, D, L

Alarm output when opening

CA

Output

BOOL

I, Q, M, D, L

Alarm output when closing

Q

Output

BOOL

I, Q, M, D, L

A signal state of "0" indicates an error condition.

ET

Static

DINT

D, L or constant

Currently elapsed time, where one count = 1 ms

PT

Static

DINT

D, L or constant

Preset timer value, where one clock pulse = 1 ms

PREV_TIME

Static

DWORD

D, L or constant

Previous system time

O_HIS

Static

BOOL

D, L or constant

"Open" history bit

C_HIS

Static

BOOL

D, L or constant

"Close" history bit

Execution of the "Motor control-timer alarm" instruction

The following table shows the reactions of the "Motor control-timer alarm" instruction to the various input conditions:

Input parameters

Output parameters

ET

O_HIS

C_HIS

O_CMD

C_CMD

S_CMD

O_FB

C_FB

OO

CO

OA

CA

ET

O_HIS

C_HIS

Q

Status

X

1

1

X

X

X

X

X

0

0

1

1

PT

0

0

0

Alarm

X

X

X

X

X

X

1

1

0

0

1

1

PT

0

0

0

Alarm

X

X

X

X

X

1

X

X

0

0

0

0

X

0

0

1

Stop

X

X

X

1

1

X

X

X

0

0

0

0

X

0

0

1

Stop

X

0

X

1

0

0

X

X

1

0

0

0

0

1

0

1

Start opening

<PT

1

0

X

0

0

0

X

1

0

0

0

INC

1

0

1

Open

X

1

0

X

0

0

1

0

0

0

0

0

PT

1

0

1

Opened

>=PT

1

0

X

0

0

0

X

0

0

1

0

PT

1

0

0

Opening alarm

X

X

0

0

1

0

X

X

0

1

0

0

0

0

1

1

Start closing

<PT

0

1

0

X

0

X

0

0

1

0

0

INC

0

1

1

Close

X

0

1

0

X

0

0

1

0

0

0

0

PT

0

1

1

Closed

>=PT

0

1

0

X

0

X

0

0

0

0

1

PT

0

1

0

Closing alarm

X

0

0

0

0

0

X

X

0

0

0

0

X

0

0

1

Stopped

Legend:

INC

Add the time difference (ms) since the last processing of the FB to ET

PT

PT is set to the same value as ET

X

Cannot be used

<PT

ET < PT

>=PT

ET >= PT

If the input parameters O_HIS and C_HIS both have the signal state "1", they are immediately set to signal state "0". In this case, the last row in the table (X) mentioned above is valid. Because it is therefore no longer possible to check whether the input parameters O_HIS and C_HIS have the signal state "1", the output parameters are set as follows in this case:

OO = FALSE

CO = FALSE

OA = FALSE

CA = FALSE

ET = PT

Q = TRUE

Example

The following example shows how the instruction works:

Note

You can initialize static parameters in the data block.

The following tables show how the instruction works using specific values.

Before processing

In this example, the following values are used for the input and output parameters:

Parameters

Operand

Value

O_CMD

Tag_Input_O_CMD

TRUE

C_CMD

Tag_Input_C_CMD

FALSE

S_CMD

Tag_Input_S_CMD

FALSE

O_FB

Tag_Input_O_FB

FALSE

C_FB

Tag_Input_C_FB

FALSE

OO

Tag_OutputOpen

FALSE

CO

Tag_OutputClosed

FALSE

OA

Tag_Output_OA

FALSE

CA

Tag_Output_CA

FALSE

Q

Tag_Output_Q

FALSE

The following values are saved in the instance data block "MCAT_DB" of the instruction:

Parameters

Address

Value

ET

DBD4

L#2

PT

DBD8

L#22

O_HIS

DBX16.0

TRUE

C_HIS

DBX16.1

FALSE

After processing

The following values are written to the output parameters after the instruction has been executed:

Parameters

Operand

Value

OO

Tag_OutputOpen

TRUE

CO

Tag_OutputClosed

FALSE

OA

Tag_Output_OA

FALSE

CA

Tag_Output_CA

FALSE

Q

Tag_Output_Q

TRUE

The following values are saved in the instance data block "MCAT_DB" of the instruction:

Parameters

Address

Value

ET

DBD4

L#0

O_HIS

DBX16.0

TRUE

CMD_HIS

DBX16.1

FALSE