EQ_Type: Compare data type for EQUAL with the data type of a tag (S7-1200, S7-1500) - STEP 7

FBD (S7-1200, S7-1500)

ft:publication_title
FBD (S7-1200, S7-1500)
Product
STEP 7
Version
V20
Publication date
11/2024
Language
en-US
EQ_Type: Compare data type for EQUAL with the data type of a tag

Description

You can use the "Compare data type for EQUAL with the data type of a tag" instruction to query the data type of a tag to which a VARIANT points. You are comparing the data type of the tag at IN1 parameter, which you declared in the block interface, with the data type of a tag at IN2 parameter for "Equal".

The tag at the IN1 parameter must have the VARIANT data type. The tag at the IN2 parameter can be an elementary data type or a PLC data type.

If the condition of the comparison is fulfilled, the instruction returns the result of logic operation (RLO) "1". If the comparison condition is not fulfilled, the instruction returns RLO "0".

Comparison of timers, date and time

Not all times can be compared directly with each other, such as S5TIME. In this case they are implicitly converted into another time so that they can be compared, for example to TIME.

If you want to compare dates and times of different data types, the value of the smaller date or time data type is implicitly converted into the larger date or time data type. This means the two date and time data types DATE and DTL, for example, are compared on the basis of DTL.

When the implicit conversions fail, the comparison result is FALSE.

Comparison of structures

For the comparison of structures, you can use the instruction "CMP ==". Anonymous structures cannot generally be compared unless they are part of the same ARRAY.

For additional information on the comparison of structures, please refer to: CMP ==: Equal

Parameters

The following table shows the parameters of the "Compare data type for EQUAL with the data type of a tag" instruction:

Parameters

Declaration

Data type

Memory area

Description

S7-1200

S7-1500

IN1

Input

VARIANT

L (The declaration is possible in the "Input", "InOut" and "Temp" sections of the block interface.)

First operand

IN2

Input

Bit sequences, integers, floating-point numbers, timers, date and time, character strings, ARRAY, PLC data types

I, Q, M, D, L

I, Q, M, D, L, P

Second operand

OUT

Output

BOOL

I, Q, M, D, L

I, Q, M, D, L

Result of comparison

Example

The following example shows how the instruction works:

The "TagOut" output is set when the following conditions are fulfilled:

  • The operand "TagIn" has the signal state "1".

  • The condition of the comparison instruction is fulfilled, i.e. the #Tag1 operand is equal to "Tag2".