Configuring time-of-day synchronization

Time-of-day synchronization roles of the communications module

With the time-of-day synchronization parameters, you specify the role of the communications module in the forwarding of time-of-day frames.

Depending on the mode of the module on PROFIBUS, the following synchronization roles can be set:

  • The communications module is passive node on PROFIBUS (for example DP slave):

    • Slave

    • None

  • The communications module is an active node on PROFIBUS:

    • Master

    • Slave

    • None

Meaning of the parameters

The parameters of the time-of-day synchronization have the following meaning.

  • Type of synchronization

    The parameter specifies the synchronization role:

    • Slave

      The CM clock is synchronized with another clock. The synchronization frames come from PROFIBUS. With this type of synchronization, the CM forwards the time-of-day frames to the station at a fixed interval.

      Within the S7 station, there may be only one time-of-day slave.

    • Master

      The clerk of the communications module as master sends time-of-day frames to the PROFIBUS network.

      If the synchronization type "Master" is set, the interval for outputting time-of-day frames can be selected.

    • None

      There is no synchronization.

    If more than one module with a clock is present within a network, you need to specify which module will act as the time master and which as the time slave for time-of-day synchronization purposes. There can only be one time-of-day master.

  • Update cycle

    With the synchronization role "Master", the parameter defines the update interval at which the time-of-day frames are output to the network.